B305: Overload Setting (%)
Set this parameter as % of the rated motor current. Changing of this parameter will change the
tripping time of the thermal overload curves. For example, at overload setting of 105% - Class 30
curve will trip the unit in 30sec @600% of FLC where as at 52% of overload setting – Class 30 curve
will trip the unit in 30sec @300% of FLC.
5
6
B306: Overload Curve Selection
Choose the Overload curves for the motor ‘Thermal Overload Protection’.
1. Class 30
2. Class 20
3. Class 10
4. Class 2
7
Program the appropriate class according to the characteristics of the motor and load. These trip
curves are based on a common tripping point of 600% of rated motor current. For example Class20 curve is 20-sec trip at @600% of FLC with overload setting 0f 105%.
Note: These are the cold start curve and every ‘start’ will reduced the tripping times. Curves are
shown at the overload setting of 105% in Fig. 6-6-23.