Download EST3 Programming Manual
Transcript
Output commands Disable Use the Disable command to inhibit the automatic or manual control of a system hardware component, circuit, or logic group. The Disable command requires that you specify a device type or an object label, or both. Disable device_type 'object_label' ; Parameter Description device_type Specifies the device type of the device responding to the command. Valid device types are: 12SW/12LED, 12SW/24LED, 24LED, 3-AADC, 3-ASU, 3-DSDC, 3-FTCU, 3-IDC8/4, 3-OPS, 3SW/3LEDX6, Amp, And, Audible, CheckIn, CommonAlarmOutput, CommonMonitorOutput, CommonSupervisoryOutput, DamperControl, DamperFeedback, DoorControl, DoorFeedback, Emergency, FanControl, FanFeedback, Firephone, Gatevalve, GenAlarm, GenSmoke, Guard, GuardPatrol, Heat, LED, LocalAlarm, LocalMonitor, LocalRelay, LocalTrouble, Matrix, Monitor, NonsupervisedOutput, NSCommonAlarmOutput, NSCommonMonitorOutput, NSCommonSupervisoryOutput, NSCommonTroubleOutput, Power, Pull, Security, Smoke, SmokeVfy, SprinklerSupervisory, StageOne, StageTwo, SupervisedOutput, Supervisory, Switch, Tamper, Temperature, Text, TimeControl, Visible, Waterflow, Zone 'object_label' Specifies the label of the output device responding to the command. Note: Disabling a Zone group disables the group and all the devices in the group. Example [CIRCUIT_DISABLE] SW 'PANEL_1_SW1': DISABLE DSDC 'SIGA_CIRCUIT_1'; EST3 Programming Manual Technical Manuals Online! - http://www.tech-man.com 3.21