Download SIGA-REL Technical Reference Manual
Transcript
Installing the SIGA-REL Environmental conditions Operating temperature 32 to 120 °F (0 to 49 °C) Storage temperature -4 to 140 °F (-20 to 60 °C) Humidity 0 to 93% RH, non-condensing Table 1-5: Power riser Total riser current (Amps) Distance from SIGA-REL to power supply #12 AWG 2.5 mm2 #14 AWG 1.5 mm2 Wire resistance (W per wire) 4.0 29 ft 8.84 m 20 ft 6.10 m 0.050 3.5 34 ft 10.36 m 23 ft 7.01 m 0.057 3.0 39 ft 11.89 m 27 ft 8.23 m 0.067 2.5 47 ft 14.33 m 32 ft 9.75 m 0.080 2.0 59 ft 17.98 m 40 ft 12.19 m 0.100 1.5 78 ft 23.77 m 53 ft 16.15 m 0.133 1.0 118 ft 35.97 m 80 ft 24.38 m 0.200 Table 1-6: Prerelease and release circuits (per circuit) Total riser current (Amps) 1.8 Distance from SIGA-REL to signals #12 AWG 2.5 mm2 #14 AWG 1.5 mm2 Wire resistance (W per wire) 2.00 176 ft 53.64 m 120 ft 36.58 m 0.300 1.75 202 ft 61.57 m 137 ft 41.76 m 0.343 1.50 235 ft 71.63 m 160 ft 48.77 m 0.400 1.25 282 ft 85.95 m 192 ft 58.52 m 0.480 1.00 353 ft 107.59 m 240 ft 73.15 m 0.600 0.50 706 ft 215.19 m 480 ft 146.30 m 1.200 SIGA-REL Technical Reference Manual