Download EST3 Programming Manual

Transcript
Output commands
Disable
Use the Disable command to inhibit the automatic or manual
control of a system hardware component, circuit, or logic group.
The Disable command requires that you specify a device type or
an object label, or both.
Disable device_type 'object_label' ;
Parameter
Description
device_type
Specifies the device type of the device
responding to the command. Valid device types
are:
12SW/12LED, 12SW/24LED, 24LED, 3-AADC,
3-ASU, 3-DSDC, 3-FTCU, 3-IDC8/4, 3-OPS,
3SW/3LEDX6, Amp, And, Audible, CheckIn,
CommonAlarmOutput, CommonMonitorOutput,
CommonSupervisoryOutput, DamperControl,
DamperFeedback, DoorControl, DoorFeedback,
Emergency, FanControl, FanFeedback,
Firephone, Gatevalve, GenAlarm, GenSmoke,
Guard, GuardPatrol, Heat, LED, LocalAlarm,
LocalMonitor, LocalRelay, LocalTrouble, Matrix,
Monitor, NonsupervisedOutput,
NSCommonAlarmOutput,
NSCommonMonitorOutput,
NSCommonSupervisoryOutput,
NSCommonTroubleOutput, Power, Pull,
Security, Smoke, SmokeVfy,
SprinklerSupervisory, StageOne, StageTwo,
SupervisedOutput, Supervisory, Switch, Tamper,
Temperature, Text, TimeControl, Visible,
Waterflow, Zone
'object_label'
Specifies the label of the output device
responding to the command.
Note: Disabling a Zone group disables the group and all the
devices in the group.
Example
[CIRCUIT_DISABLE]
SW 'PANEL_1_SW1':
DISABLE DSDC 'SIGA_CIRCUIT_1';
EST3 Programming Manual
Technical Manuals Online! - http://www.tech-man.com
3.21