Chapter 1 – Introduction to IAQ and Ventilation Control

Plastics in furniture

Computers

Plants
These materials emit a high level of VOCs when they are new. That is why it is often
noticeable when a building is newly constructed, renovated or even painted. These materials
continuously emit VOCs. Over time, the rate of emitting VOCs in most materials decline with
age. The rate of emitting VOCs drops dramatically over the first few weeks of use or
installation. Then over the first few years, the emitting rate continues to drop to a lower level.
Eventually, it drops to a consistent rate. That is why guidelines are written to purge new
construction buildings in order to eliminate the highest concentration of VOCs and some
guidelines call for increasing ventilation for a year or two.
Many of these materials are now becoming available in low-emitting versions. Even so, the
design engineer must design an amount of ventilation to dilute the anticipated VOC levels.
Most jurisdictions and professionals reference ASHRAE Standard 62.1 to determine the
amount of ventilation needed for dilution of the Interior Design Component.
In the ASHRAE 62.1 standard, table 6-1 defines a factor called “Area Outdoor Air Rate (Ra)”.
There are a variety of values that correspond to different types of spaces. The values guide
the engineer to a ventilation rate per square foot of space. The design engineer can also, at
his discretion, add design factors for special cases, such as high concentration of painted
walls, high concentration of computers, or high concentration of art materials such as
architects or designers offices. The design engineer cumulates the ventilation rates for all of
the spaces to determine a ventilation rate for the area.
Role of Population in Ventilation
Humans are another source of contaminants. Ventilation is intended to dilute odorous
bioeffluents from occupants and other sensory contaminants that result directly from
occupant activities. It is proportional to the number of people expected to occupy the space.
These include:

Metabolic odors

Odors from clothes, shoes and coats

Odors from lotions, perfumes and hair products

Food odors

Machines that humans use, such as copiers and printers
Up until 1999, the guidelines for ventilation were to predict the normal population of a
building. More specifically, the design engineer anticipated the normal or maximum
population of each space and added them up. This often resulted in highly ventilated spaces.
This was not a problem for IAQ, but the cost of the ventilation was higher than it needed to
be.
In 1999, an updated version of ASHRAE 62.1 was issued that allowed for changing
ventilation base on predictable or sensed changes in population. Thus, the ventilation rate
could change based on the demand. This is the establishment of Demand Control Ventilation.
Further refinements to DCV methods were issued in 2001, 2004, 2007 and 2010.