Download Applications Engineering Manual - EarthWise Intelligent Variable Air
Transcript
Primary System Components Table 3. AHRI/ISO 13256–1 Standard Rating Conditions for Water-to-Air Heat Pumps Water-source heat pumps Ground-source heat pumps Ground-water heat pumps Cooling mode Airflow rate specified by the manufacturer Entering air dry-bulb temperature 80.6°F (27°C) 80.6°F (27°C) 80.6°F (27°C) Entering air wet-bulb temperature 66.2°F (19°C) 66.2°F (19°C) 66.2°F (19°C) External static pressure 0 in. H2O (0 Pa) 0 in. H2O (0 Pa) 0 in. H2O (0 Pa) Liquid flow rate specified by the manufacturer Entering liquid temperature 86°F (30°C) 77°F (25°C) 59°F (15°C) Heating mode Airflow rate specified by the manufacturer Entering air dry-bulb temperature 68°F (20°C) 68°F (20°C) 68°F (20°C) Entering air wet-bulb temperature 59°F (15°C) 59°F (15°C) 59°F (15°C) External static pressure 0 in. H2O (0 Pa) 0 in. H2O (0 Pa) 0 in. H2O (0 Pa) Liquid flow rate specified by the manufacturer Entering liquid temperature 68°F (20°C) 32°F (0°C) 50°F (10°C) Notice that neither the airflow rate nor the liquid flow rate is specified by the standard. Rather, they are left to the discretion of the manufacturer. Since these factors can significantly impact the performance of a WSHP, use caution when comparing the performance of one manufacturer to another. As an example, one manufacturer’s 3-ton (11-kW) heat pump may be rated at a liquid flow rate of 8.4 gpm (0.53 L/s), while another manufacturer may rate the same-size unit using 9 gpm (0.57 L/s). The heat pump will operate more efficiently with the higher flow rate, but system pumping energy will also increase. While the 0.6 gpm (0.04 L/s) difference in this example may seem small, this 7 percent increase in flow adds up when you consider that the system may be comprised of 50 or 100 heat pumps. Table 4. AHRI/ISO 13256–2 Standard Rating Conditions for Water-to-Water Heat Pumps Water-source heat pumps Ground-source heat pumps Ground-water heat pumps Cooling mode “Load-side” liquid flow rate specified by the manufacturer “Load-side” entering liquid temperature 53.6°F (12°C) “Source-side” liquid flow rate 53.6°F (12°C) 53.6°F (12°C) specified by the manufacturer “Source-side” entering liquid temperature 86°F (30°C) 77°F (25°C) 59°F (15°C) Heating mode “Load-side” liquid flow rate specified by the manufacturer “Load-side” entering liquid temperature 104°F (40°C) “Source-side” liquid flow rate “Source-side” entering liquid temperature SYS-APM010-EN 104°F (40°C) 104°F (40°C) specified by the manufacturer 68°F (20°C) 32°F (0°C) Water-Source and Ground-Source Heat Pump Systems 50°F (10°C) 31