Primary System Components
Table 3.
AHRI/ISO 13256–1 Standard Rating Conditions for Water-to-Air Heat Pumps
Water-source heat pumps
Ground-source heat pumps
Ground-water heat pumps
Cooling mode
Airflow rate
specified by the manufacturer
Entering air dry-bulb temperature
80.6°F (27°C)
80.6°F (27°C)
80.6°F (27°C)
Entering air wet-bulb temperature
66.2°F (19°C)
66.2°F (19°C)
66.2°F (19°C)
External static pressure
0 in. H2O (0 Pa)
0 in. H2O (0 Pa)
0 in. H2O (0 Pa)
Liquid flow rate
specified by the manufacturer
Entering liquid temperature
86°F (30°C)
77°F (25°C)
59°F (15°C)
Heating mode
Airflow rate
specified by the manufacturer
Entering air dry-bulb temperature
68°F (20°C)
68°F (20°C)
68°F (20°C)
Entering air wet-bulb temperature
59°F (15°C)
59°F (15°C)
59°F (15°C)
External static pressure
0 in. H2O (0 Pa)
0 in. H2O (0 Pa)
0 in. H2O (0 Pa)
Liquid flow rate
specified by the manufacturer
Entering liquid temperature
68°F (20°C)
32°F (0°C)
50°F (10°C)
Notice that neither the airflow rate nor the liquid flow rate is specified by the
standard. Rather, they are left to the discretion of the manufacturer. Since
these factors can significantly impact the performance of a WSHP, use
caution when comparing the performance of one manufacturer to another.
As an example, one manufacturer’s 3-ton (11-kW) heat pump may be rated at
a liquid flow rate of 8.4 gpm (0.53 L/s), while another manufacturer may rate
the same-size unit using 9 gpm (0.57 L/s). The heat pump will operate more
efficiently with the higher flow rate, but system pumping energy will also
increase. While the 0.6 gpm (0.04 L/s) difference in this example may seem
small, this 7 percent increase in flow adds up when you consider that the
system may be comprised of 50 or 100 heat pumps.
Table 4.
AHRI/ISO 13256–2 Standard Rating Conditions for Water-to-Water Heat Pumps
Water-source heat pumps
Ground-source heat pumps
Ground-water heat pumps
Cooling mode
“Load-side” liquid flow rate
specified by the manufacturer
“Load-side” entering liquid temperature
53.6°F (12°C)
“Source-side” liquid flow rate
53.6°F (12°C)
53.6°F (12°C)
specified by the manufacturer
“Source-side” entering liquid temperature
86°F (30°C)
77°F (25°C)
59°F (15°C)
Heating mode
“Load-side” liquid flow rate
specified by the manufacturer
“Load-side” entering liquid temperature
104°F (40°C)
“Source-side” liquid flow rate
“Source-side” entering liquid temperature
SYS-APM010-EN
104°F (40°C)
104°F (40°C)
specified by the manufacturer
68°F (20°C)
32°F (0°C)
Water-Source and Ground-Source Heat Pump Systems
50°F (10°C)