Chapter 5 Function parameter Code F6.01 Parameter name Setting range 0 to 0xFFFF BIT0: Running frequency BIT1: Set frequency BIT2: Bus voltage BIT3: Output voltage BIT4: Output current BIT5: Running speed BIT6: Output power Running status display BIT7: Output torque parameters selection BIT8: PID setting value BIT9: PID feedback value BIT10: Input terminal status BIT11: Output terminal status BIT12: Analog AI1 value BIT13: Analog AI2 value BIT14: Current stage of multispeed BIT15: Torque set value Factory Change default 03FF ☆ When the inverter is in operation, the parameter display is limited by F6.01, that is 16-bit binary string, if a bit is 1, the parameters corresponding to the bit can be viewed by SHIFT key during operation. If a bit is 0, the parameters corresponding to the bit will not display. To set function code F6.01, a binary number must be converted into a hexadecimal number, and then enter the function code. F6.02 Stop status display parameters selection 1 to 0x3FF BIT0: Set frequency BIT1: Bus voltage BIT2: Input terminal status BIT3: Output terminal status BIT4: PID setting value BIT5: PID feedback value BIT6: Analog AI1 value BIT7: Analog AI2 value BIT8: Current stage of multispeed BIT9: Torque set value. BIT10 to BIT15: Reserved 0FF ☆ The setting on this function is same with F6.01 setting. When PI130 series inverter stops, the parameters display is effected by this function code. F6.03 Speed display coefficient 0.1 to 999.9% Mechanical speed = 120 * running frequency * F6.03/number of motor pole pairs. 100.0% ☆ Mechanical speed = 120 * running frequency * F6.03/number of motor pole pairs, this function code is used to correct speed scale display error, has not affect to the actual speed. 66