Load Breaker Hot Connections
Connect load breaker hot connections.
1. Secure cables with two hole lugs to the 1/4" studs on 5/8" centers using the supplied hardware.
2. Run cables directly out the rear of the distribution center above the breaker return cables.
Make Hot
Connection Second
Make Return
Connection First
Figure 18 — Battery, load, and return connection locations (with battery and load breakers shown)
7.5 Alarm and Signal Connection
7.5.1 Breaker Alarm and Bus Voltage Connections
1. Locate the terminal block on the rear of the CXDM-E2. Refer to Figure 9 and the schematic drawing at the
end of this manual for details on terminal block assignments.
2. Connect these alarms and signals to the local alarm-sending unit. Use wire sizes #20 to #26 AWG (0.518 to
0.14mm²).
Bus A
Voltage (+)
Bus A
Voltage (-)
Bus B
Voltage (+)
Bus B
Voltage (-)
Bus A
Breaker
Alarm (NC)
Bus B
Breaker
Alarm (NC)
Bus A
Breaker
Alarm (COM)
Bus B
Breaker
Alarm (COM)
Bus A Breaker
Alarm (NO)
Bus B Breaker
Alarm (NO)
Left (Bus A) Connection
Right (Bus B) Connection
Figure 19 — Battery, load, and return connection locations (with battery and load breakers shown)
26
9400011-J0 Rev A