Download Model HXS10 Application Specific Controller
Transcript
4. Hardware Specifications ▌ DIN rail mounting Mounting to DIN rail Hook areas (A) of the DIN rail mounting brackets (right and left) on a DIN rail and push the HXS10 forward. (A) Input sampling period Burnout detection This instrument is designed to measure circuits that are not directly WARNING connected to the mains. Do not use it for measurements that fall under Measurement Category II, III, or IV. Input bias current Measured current (RTD) Input resistance DIN Rail Entrance IV Cable Push Category Removing from DIN rail While pressing the latch levers downward, pull the HXS10 toward you to release it from the rail. Push Measurement category II CAT.II III CAT.III IV CAT.IV Internal Wiring II III T O Outlet Description For measurements performed on circuits directly connected to the low-voltage installation. For measurements performed in the building installation. For measurements performed at the source of the low-voltage installation. Remarks Appliances, portable equipments, etc. Distribution board, circuit breaker, etc. Overhead wire, cable systems, etc. Latch levers Latch lever Push ▌ Input/Output Specifications ● Analog Input (AI) Latch • Number of Universal Inputs: Max. 6 (M3 screw terminal) • Input range: -5% to 105% (The guaranteed accuracy range is 0% to 100%.) • Input type, instrument range, and measurement accuracy: See the table below, Input Type Pull ▌ Wall mounting Remove the DIN rail mounting brackets from the rear of the HXS10 and then mount the HXS10 to the wall surface using four M4 screws. Removing the DIN rail mounting brackets The DIN rail mounting brackets can be removed from the instrument by unscrewing the M3 mounting screws (two places each) as shown below. DIN rail mounting bracket M3 mounting screws To attach the DIN rail brackets to the instrument, fasten them with M3 mounting screws (two places each) as shown above. (Tightening torque: 0.6N·m) Mounting to the wall Fix the instrument to the wall with four M4 screws. Range Measurable range Accuracy name (Range code) DC voltage 20 mV 20 mV (0) -20.000 to 20.000 mV ±0.05% of instrument range ±1 µV 60 mV 60 mV (1) -60.00 to 60.00 mV ±0.05% of instrument range ±10 µV 200 mV 200 mV (2) -200.00 to 200.00 mV 1V 1 V (3) -1.0000 to 1.0000 V ±0.05% of instrument range ±0.1 mV 2V 2 V (4) -2.0000 to 2.0000 V 6V 6 V (5) -6.000 to 6.000 V ±0.05% of instrument range ±1 mV 0-10 V 0-10 V (6) 0.000 to 10.000 V ±0.1% of instrument range ±1 mV 20 V 20 V (7) -20.000 to 20.000 V ±0.05% of instrument range ±1 mV Standard 0.4-2 V 0.4-2 V (8) 0.4000 to 2.0000 V ±0.1% of instrument range ±0.1 mV signal 1-5 V 1-5 (9) 1.000 to 5.000 V ±0.1% of instrument range ±1 mV K1 (10) Thermocouple K -270.0 to -450.0 to ± 0.1% of instrument range ± 0.1°C (*1) 370.0°C 2500.0°F for 0°C or more . K2 (11) -200.0 to -200.0 to ± 0.2% of instrument range ± 0.1°C 500.0°C 1000.0°F for less than 0°C J J (12) -200.0 to -300.0 to ± 2% of instrument range ± 0.1°C 1100.0°C 2000.0°F for less than -200°C of thermocouple T T (13) -270.0 to -450.0 to K, T. 400.0°C 750.0°F 32 to ± 0.15% of instrument range ± 0.1°C B B (14) 0.0 to 1800.0°C 3300°F for 400°C or more ± 5% of instrument range ± 0.1°C for less than 400°C 32 to ± 0.15% of instrument range ± 0.1°C S S (15) 0.0 to 1700.0°C 3100°F R R (16) 0.0 to 32 to 1700.0°C 3100°F N N (17) -200.0 to -300.0 to ± 0.1% of instrument range ± 0.1°C 1300.0°C 2400.0°F for 0°C or more ± 0.25% of instrument range ± 0.1°C for less than 0°C E E (18) -270.0 to -450.0 to ± 0.1% of instrument range ±0.1°C 800.0°C 1450.0°F for 0°C or more L L (19) -200.0 to -300.0 to ± 0.2% of instrument range ± 0.1°C 900.0°C 1600.0°F for less than 0°C U U (20) -200.0 to -300.0 to ± 1.5% of instrument range ± 0.1°C 400.0°C 750.0°F for less than -200°C of thermocouple E 32 to ± 0.2% of instrument range ± 0.1°C W W (21) 0.0 to 2300.0°C 4200°F Platinel 2 PL2 (22) 0.0 to 32.0 to ± 0.1% of instrument range ± 0.1°C 1390.0°C 2500.0°F PR20-40 P2040 (23) 0.0 to 32 to ± 0.5% of instrument range ± 0.1°C 1900.0°C 3400°F for 800°C or more Accuracy is not guaranteed for less than 800°C W97Re3- WRe (24) 0.0 to 32 to ± 0.2% of instrument range ±0.1°C W75Re25 2000.0°C 3600°F RTD JPt100 JPT1 (25) -200.0 to -300.0 to ± 0.1% of instrument range ± 0.1°C 500.0°C 1000.0°F (*2) JPT2 (26) -150.00 to -200.0 to ± 0.1% of instrument range ± 0.1°C 150.00°C 300.0°F Pt100 PT1 (27) -200.0 to -300.0 to ± 0.1% of instrument range ± 0.1°C 850.0°C 1560.0°F (*2) PT2 (28) -150.00 to -200.0 to ± 0.1% of instrument range ± 0.1°C 150.00°C 300.0°F K,J,T,B,S,R,N,E:IEC584-1(1995) DIN IEC584 JIS C1602-1995 U: Cu-CuNi,DIN43710, L:Fe-CuNi,DIN43710 W:W-5% Re/W-26% Re(Hoskins Mfg.Co.),ASTM E988 W97Re3-W75Re25: W-3%Re/W-25%Re (Hoskins Mfg. Co.) Pt100:JIS C1604-1997 IEC751-1995 DIN IEC751-1996 JPt100:JIS C1604-1989 JIS C1606-1989 Measuring current i=1 mA The accuracy is that in the standard operating conditions: 23±2°C, 55±10%RH, and power voltage at 24 VDC ±10%. *1: Excluding reference junction compensation errors. *2: ±0.4°C in the range between 0 and +100°C, ±0.6°C in the range between -100 to +200°C, ±0.8°C in the range between +200 to +500°C • M4 mounting screws (four places) Recommended tightening torque: 1.2N·m Synchronous with control period 100 ms or 250 ms (Analog Input 2 channels) 250 ms (Analog Input 4 channels or 6 channels) • Functions at TC, RTD, and standard signal. • Detection ON/OFF switchable (settable for each channel) • Upscale, downscale, and off can be specified. • If “OFF” is specified, analog input value is undefined. • For standard signal, burnout is determined to have occurred if it is less than 0.1 V. • Detection time (max): 2 sec. 10 nA or less (except the case of setting burnout detection) About 1 mA 10 MΩ or more (for TC / DC voltage (1 V range or less)) About 1 MΩ (for DC voltage (2 V range or more) / standard signal) 2 kΩ or less Allowable signal source resistance Effects of ±10 µV/1 kΩ or less (Thermocouple, RTD signal source (for TC / DC voltage (1 V range or less)) and Standard signal) resistance ±0.15%/1 kΩ or less (for DC voltage (2 V range or more) / standard signal) Allowable wiring RTD input: Max. 10 Ω/wire resistance (RTD) (The conductor resistance between three wires shall be equal.) Wiring resistance effect: ±0.1°C/10 Ω (The conductor resistance between three wires shall be equal.) The variation due to a difference in resistance between conductors, 40 mΩ (maximum difference between three wires), is approx. 0.1°C. Allowable input ±10 V DC (for TC / DC voltage (1 V range or less) / RTD input) voltage ±30 V DC (for DC voltage (2 V range or less) / standard signal) Noise rejection ratio 40 dB or more (at 50/60 Hz) (Normal mode) (*1) 120 dB or more (at 50/60 Hz) (Common mode) Maximum common 250 V ACrms or less mode noise voltage 250 V ACrms or less Maximum interchannel noise voltage Reference junction ±1.5°C (15 to 35°C) compensation error ±2.0°C (-10 to 15°C and 35 to 50°C) ±2.5°C (-20 to -10°C and 50 to 70°C) Effect of ambient ±0.01% of instrument range /°C temperature ● Digital Output (DO) Number of outputs Output type Isolation method Rated load voltage Maximum load current On-voltage Leakage current at OFF External power supply External connection Address setting (Setting Range) Rate Communication method Data length Start bit Stop bit Parity Protocol Step Response Time Within 500 ms (for computation period 100 ms) (63% of analog output response time when a step change of 10 to 90% of input span is applied) Within 1.5 s (for computation period 250 ms) (63% of analog output response time when a step change of 10 to 90% of input span is applied) ● Digital Input (DI) 10 BASE-T / 100 BASE-TX 10/100 Mbps (automatic) RJ-45 100 m max Modbus/TCP client, Modbus/TCP server, SNTP client and SNTP server 1 to 247 (RS-485) , fixed 1 (RS-232) (Use the setting software) 1200/2400/4800/9600/19200/38400/57600/115200 bps Asynchronous communication method 8 bit 1 bit 1 bit/2 bits ODD/EVEN/NONE Modbus RTU master or Modbus RTU slave RS-232 Network topology Modes of operation Hardware handshaking Connector type Maximum distance 1:1 full-duplex none DSUB-9pin max. 15 m RS-485 Network Topology Modes of operation Connector type Maximum distance Terminating resistors 1:n multidrop, max. n=31 Half-duplex by using two wires 4 pole terminal 1.2 km max External (220 Ω, 1/4 W or more) ● Maintenance communication Using the PC software, configuration parameter data, programming, F/W download can be realized through this port. Number of ports Connector Cable Interface Supported Driver OS 1 Micro-USB (Micro-B) USB-TTL conversion cable (HXSS90) Compliant with USB1.1 Windows XP Professional (Service Pack2 or later) (32 bit version) Windows Vista Business (Service Pack1 or later) (32 bit version) Windows 7 Professional (32 bit version) ▌ Safety and EMC Standards IEC/EN61010-1, IEC/EN61010-2-030. Installation category Pollution degree Measurement category Rated measurement input voltage Rated transient overvoltage ● Pulse counter Input (Encoder Input) Number of channels 2 channels Input pulse method Incremental encoder Input pulse rate 10000 (pulse/s) (phase A/phase B (single multiplication)) 20000 (pulse/s) (phase A/phase B (double multiplication)) 40000 (pulse/s) (phase A/phase B (quad multiplication)) Corresponding Complementary output (push/pull) / Differential output encoder output Rated input voltage 24 V±20% (19.2 to 28.8 V : operating voltage range) Rated input current 5 mA or less On-voltage / On14 V DC or more / 1.6 mA or more current Off-voltage / Off2 V DC or more / 0.25 mA or more current External connection 2.54 mm-pitch clamp terminal (recommended tightening torque: 0.12 – 0.15 N·m) Applicable wires: 0.14 to 0.5 mm2 (AWG26 to AWG20) Stripped wire length: 4.5 mm compliant with IEEE 802.3 ● Serial Communication (RS-232/RS-485) ● Step Response Time 12 DC voltage input (used for sink and source), open collector or no-voltage contact input (External DI-driven power supply) Insulating Photo-coupler isolation (internal circuit – input) Rated current (input) About 1.4 mA /1 digital input Rated input voltage 24VDC -15%, +10% Input resistance About 16.5 kΩ ON/OFF detection Voltage input On-voltage / 17 V DC or more / 1 mA or more On-current Off-voltage / 4 V DC or less / 250 µA or less Off-current Open collector Input voltage of 2 V DC or less is determined as “ON” input and leakage current must not exceed 250 µA when “OFF.” No-voltage Contact resistance of 1 kΩ or less is determined as “ON” contact input and contact resistance of 100 kΩ or more as “OFF.” External connection 2.54 mm-pitch clamp terminal (recommended tightening torque: 0.12 – 0.15 N·m) Applicable wires: 0.14 to 0.5 mm2 (AWG26 to AWG20) Stripped wire length: 4.5 mm 2.54 mm-pitch clamp terminal (recommended tightening torque: 0.12 – 0.15 N·m) Applicable wires: 0.14 to 0.5 mm2 (AWG26 to AWG20) Stripped wire length: 4.5 mm Communication standard Transmission type Rate Connector type Segment Protocol 2 (M3 screw terminal) Current output: 4 to 20 mA DC or 0 to 20 mA DC 600 Ω or less ±0.1% of span (±5% of span for 1 mA or less) The accuracy is that in the standard operating conditions: 23±2°C, 55±10%RH. ±0.02% of F.S./°C or less Number of inputs Input type 12 to 24 V DC (10.2 to 26.4 V DC) 20 mA or more ● Ethernet Communication ● Analog Output (AO) Effect of ambient temperature 0.6 V DC or less 0.1 mA or less ▌ Communication Specifications *1: With digital filter set Number of outputs Output type Load resistance Output accuracy 12 (Note : DO12 is used for DO12 and FAIL output.) Transistor contact output (SINK: Share a common wire with the external power supply) Photo-coupler isolation (internal circuit – input) Lower than the external power supply voltage 100 mA / one DO I 2 O ±30 V DC max. 1500 V (*) * This is a reference safety value. This value is not necessarily a guarantee of instrument performance. CE marking EMC Directive EN61326-1 Class A, Table2 EN61326-2-3 EN55011 Class A Group1 * The instrument continues to operate at a measurement accuracy of within ±10% of the range during testing. EMC Regulatory Arrangement in Australia and New Zealand EN55011 Class A Group1 KC marking Electromagnetic wave interference prevention standard, electromagnetic wave protection standard compliance External Dimensions. ● Environmental resistance Compliant with RoHS, WEEE IM 25G10B01-01EN page 2/4