4. Hardware Specifications
▌ DIN rail mounting
Mounting to DIN rail
Hook areas (A) of the DIN rail mounting brackets (right and left) on a DIN rail and
push the HXS10 forward.
(A)
Input sampling
period
Burnout detection
This instrument is designed to measure circuits that are not directly
WARNING connected to the mains. Do not use it for measurements that fall
under Measurement Category II, III, or IV.
Input bias current
Measured current
(RTD)
Input resistance
DIN Rail
Entrance IV
Cable
Push
Category
Removing from DIN rail
While pressing the latch levers downward, pull the HXS10 toward you to release
it from the rail.
Push
Measurement
category
II
CAT.II
III
CAT.III
IV
CAT.IV
Internal Wiring
II
III
T
O
Outlet
Description
For measurements performed on circuits
directly connected to the low-voltage
installation.
For measurements performed in the
building installation.
For measurements performed at the source
of the low-voltage installation.
Remarks
Appliances, portable
equipments, etc.
Distribution board, circuit
breaker, etc.
Overhead wire, cable
systems, etc.
Latch levers
Latch lever
Push
▌ Input/Output Specifications
● Analog Input (AI)
Latch
• Number of Universal Inputs: Max. 6 (M3 screw terminal)
• Input range: -5% to 105% (The guaranteed accuracy range is 0% to 100%.)
• Input type, instrument range, and measurement accuracy: See the table below,
Input Type
Pull
▌ Wall mounting
Remove the DIN rail mounting brackets from the rear of the HXS10 and then
mount the HXS10 to the wall surface using four M4 screws.
Removing the DIN rail mounting brackets
The DIN rail mounting brackets can be removed from the instrument by unscrewing
the M3 mounting screws (two places each) as shown below.
DIN rail mounting bracket
M3 mounting screws
To attach the DIN rail brackets to the instrument, fasten them with M3 mounting
screws (two places each) as shown above. (Tightening torque: 0.6N·m)
Mounting to the wall
Fix the instrument to the wall with four M4 screws.
Range
Measurable range
Accuracy
name
(Range
code)
DC voltage
20 mV
20 mV (0) -20.000 to 20.000 mV ±0.05% of instrument range ±1 µV
60 mV
60 mV (1) -60.00 to 60.00 mV ±0.05% of instrument range ±10 µV
200 mV 200 mV (2) -200.00 to 200.00 mV
1V
1 V (3)
-1.0000 to 1.0000 V ±0.05% of instrument range ±0.1 mV
2V
2 V (4)
-2.0000 to 2.0000 V
6V
6 V (5)
-6.000 to 6.000 V
±0.05% of instrument range ±1 mV
0-10 V
0-10 V (6) 0.000 to 10.000 V
±0.1% of instrument range ±1 mV
20 V
20 V (7)
-20.000 to 20.000 V ±0.05% of instrument range ±1 mV
Standard
0.4-2 V
0.4-2 V (8) 0.4000 to 2.0000 V
±0.1% of instrument range ±0.1 mV
signal
1-5 V
1-5 (9)
1.000 to 5.000 V
±0.1% of instrument range ±1 mV
K1 (10)
Thermocouple K
-270.0 to -450.0 to ± 0.1% of instrument range ± 0.1°C
(*1)
370.0°C 2500.0°F for 0°C or more
.
K2 (11)
-200.0 to -200.0 to ± 0.2% of instrument range ± 0.1°C
500.0°C 1000.0°F for less than 0°C
J
J (12)
-200.0 to -300.0 to ± 2% of instrument range ± 0.1°C 1100.0°C 2000.0°F for less than -200°C of thermocouple
T
T (13)
-270.0 to -450.0 to K, T.
400.0°C 750.0°F
32 to
± 0.15% of instrument range ± 0.1°C
B
B (14)
0.0 to
1800.0°C 3300°F
for 400°C or more
± 5% of instrument range ± 0.1°C
for less than 400°C
32 to
± 0.15% of instrument range ± 0.1°C
S
S (15)
0.0 to
1700.0°C 3100°F
R
R (16)
0.0 to
32 to
1700.0°C 3100°F
N
N (17)
-200.0 to -300.0 to ± 0.1% of instrument range ± 0.1°C
1300.0°C 2400.0°F for 0°C or more
± 0.25% of instrument range ± 0.1°C
for less than 0°C
E
E (18)
-270.0 to -450.0 to ± 0.1% of instrument range ±0.1°C
800.0°C 1450.0°F for 0°C or more
L
L (19)
-200.0 to -300.0 to ± 0.2% of instrument range ± 0.1°C
900.0°C 1600.0°F for less than 0°C
U
U (20)
-200.0 to -300.0 to ± 1.5% of instrument range ± 0.1°C
400.0°C 750.0°F for less than -200°C of thermocouple E
32 to
± 0.2% of instrument range ± 0.1°C
W
W (21)
0.0 to
2300.0°C 4200°F
Platinel 2 PL2 (22) 0.0 to
32.0 to
± 0.1% of instrument range ± 0.1°C
1390.0°C 2500.0°F
PR20-40 P2040 (23) 0.0 to
32 to
± 0.5% of instrument range ± 0.1°C
1900.0°C 3400°F
for 800°C or more
Accuracy is not guaranteed
for less than 800°C
W97Re3- WRe (24) 0.0 to
32 to
± 0.2% of instrument range ±0.1°C
W75Re25
2000.0°C 3600°F
RTD
JPt100
JPT1 (25) -200.0 to -300.0 to ± 0.1% of instrument range ± 0.1°C
500.0°C 1000.0°F (*2)
JPT2 (26) -150.00 to -200.0 to ± 0.1% of instrument range ± 0.1°C
150.00°C 300.0°F
Pt100
PT1 (27) -200.0 to -300.0 to ± 0.1% of instrument range ± 0.1°C
850.0°C 1560.0°F (*2)
PT2 (28) -150.00 to -200.0 to ± 0.1% of instrument range ± 0.1°C
150.00°C 300.0°F
K,J,T,B,S,R,N,E:IEC584-1(1995) DIN IEC584 JIS C1602-1995
U: Cu-CuNi,DIN43710, L:Fe-CuNi,DIN43710
W:W-5% Re/W-26% Re(Hoskins Mfg.Co.),ASTM E988
W97Re3-W75Re25: W-3%Re/W-25%Re (Hoskins Mfg. Co.)
Pt100:JIS C1604-1997 IEC751-1995 DIN IEC751-1996
JPt100:JIS C1604-1989 JIS C1606-1989 Measuring current i=1 mA
The accuracy is that in the standard operating conditions: 23±2°C, 55±10%RH, and
power voltage at 24 VDC ±10%.
*1: Excluding reference junction compensation errors.
*2: ±0.4°C in the range between 0 and +100°C, ±0.6°C in the range between -100 to
+200°C, ±0.8°C in the range between +200 to +500°C
•
M4 mounting screws (four places)
Recommended tightening torque: 1.2N·m
Synchronous with control period
100 ms or 250 ms (Analog Input 2 channels)
250 ms (Analog Input 4 channels or 6 channels)
• Functions at TC, RTD, and standard signal.
• Detection ON/OFF switchable (settable for each channel)
• Upscale, downscale, and off can be specified.
• If “OFF” is specified, analog input value is undefined.
• For standard signal, burnout is determined to have occurred if it is less
than 0.1 V.
• Detection time (max): 2 sec.
10 nA or less (except the case of setting burnout detection)
About 1 mA
10 MΩ or more (for TC / DC voltage (1 V range or less))
About 1 MΩ (for DC voltage (2 V range or more) / standard signal)
2 kΩ or less
Allowable signal
source resistance Effects of
±10 µV/1 kΩ or less
(Thermocouple, RTD signal source (for TC / DC voltage (1 V range or less))
and Standard signal) resistance
±0.15%/1 kΩ or less
(for DC voltage (2 V range or more) / standard signal)
Allowable wiring
RTD input: Max. 10 Ω/wire
resistance (RTD)
(The conductor resistance between three wires shall be equal.)
Wiring resistance effect: ±0.1°C/10 Ω
(The conductor resistance between three wires shall be equal.)
The variation due to a difference in resistance between conductors,
40 mΩ (maximum difference between three wires), is approx. 0.1°C.
Allowable input
±10 V DC (for TC / DC voltage (1 V range or less) / RTD input)
voltage
±30 V DC (for DC voltage (2 V range or less) / standard signal)
Noise rejection ratio 40 dB or more (at 50/60 Hz) (Normal mode)
(*1)
120 dB or more (at 50/60 Hz) (Common mode)
Maximum common 250 V ACrms or less
mode noise voltage
250 V ACrms or less
Maximum interchannel noise
voltage
Reference junction ±1.5°C (15 to 35°C)
compensation error ±2.0°C (-10 to 15°C and 35 to 50°C)
±2.5°C (-20 to -10°C and 50 to 70°C)
Effect of ambient
±0.01% of instrument range /°C
temperature
● Digital Output (DO)
Number of outputs
Output type
Isolation method
Rated load voltage
Maximum load
current
On-voltage
Leakage current at
OFF
External power
supply
External connection
Address setting
(Setting Range)
Rate
Communication method
Data length
Start bit
Stop bit
Parity
Protocol
Step Response Time Within 500 ms (for computation period 100 ms) (63% of analog output
response time when a step change of 10 to 90% of input span is applied)
Within 1.5 s (for computation period 250 ms) (63% of analog output
response time when a step change of 10 to 90% of input span is applied)
● Digital Input (DI)
10 BASE-T / 100 BASE-TX
10/100 Mbps (automatic)
RJ-45
100 m max
Modbus/TCP client, Modbus/TCP server,
SNTP client and SNTP server
1 to 247 (RS-485) , fixed 1 (RS-232)
(Use the setting software)
1200/2400/4800/9600/19200/38400/57600/115200 bps
Asynchronous communication method
8 bit
1 bit
1 bit/2 bits
ODD/EVEN/NONE
Modbus RTU master or Modbus RTU slave
RS-232 Network topology
Modes of operation
Hardware handshaking
Connector type
Maximum distance
1:1
full-duplex
none
DSUB-9pin
max. 15 m
RS-485 Network Topology
Modes of operation
Connector type
Maximum distance
Terminating resistors
1:n multidrop, max. n=31
Half-duplex by using two wires
4 pole terminal
1.2 km max
External (220 Ω, 1/4 W or more)
● Maintenance communication
Using the PC software, configuration parameter data, programming, F/W download
can be realized through this port.
Number of ports
Connector
Cable
Interface
Supported Driver OS
1
Micro-USB (Micro-B)
USB-TTL conversion cable (HXSS90)
Compliant with USB1.1
Windows XP Professional (Service Pack2 or later) (32 bit version)
Windows Vista Business (Service Pack1 or later) (32 bit version)
Windows 7 Professional (32 bit version)
▌ Safety and EMC Standards
IEC/EN61010-1, IEC/EN61010-2-030.
Installation category
Pollution degree
Measurement category
Rated measurement
input voltage
Rated transient
overvoltage
● Pulse counter Input (Encoder Input)
Number of channels 2 channels
Input pulse method Incremental encoder
Input pulse rate
10000 (pulse/s) (phase A/phase B (single multiplication))
20000 (pulse/s) (phase A/phase B (double multiplication))
40000 (pulse/s) (phase A/phase B (quad multiplication))
Corresponding
Complementary output (push/pull) / Differential output
encoder output
Rated input voltage 24 V±20% (19.2 to 28.8 V : operating voltage range)
Rated input current 5 mA or less
On-voltage / On14 V DC or more / 1.6 mA or more
current
Off-voltage / Off2 V DC or more / 0.25 mA or more
current
External connection 2.54 mm-pitch clamp terminal
(recommended tightening torque: 0.12 – 0.15 N·m)
Applicable wires: 0.14 to 0.5 mm2 (AWG26 to AWG20)
Stripped wire length: 4.5 mm
compliant with IEEE 802.3
● Serial Communication (RS-232/RS-485)
● Step Response Time
12
DC voltage input (used for sink and source), open collector or no-voltage
contact input (External DI-driven power supply)
Insulating
Photo-coupler isolation (internal circuit – input)
Rated current (input) About 1.4 mA /1 digital input
Rated input voltage 24VDC -15%, +10%
Input resistance
About 16.5 kΩ
ON/OFF detection Voltage input On-voltage / 17 V DC or more / 1 mA or more
On-current
Off-voltage / 4 V DC or less / 250 µA or less
Off-current
Open collector Input voltage of 2 V DC or less is determined as “ON”
input
and leakage current must not exceed 250 µA when
“OFF.”
No-voltage
Contact resistance of 1 kΩ or less is determined as “ON”
contact input
and contact resistance of 100 kΩ or more as “OFF.”
External connection 2.54 mm-pitch clamp terminal
(recommended tightening torque: 0.12 – 0.15 N·m)
Applicable wires: 0.14 to 0.5 mm2 (AWG26 to AWG20)
Stripped wire length: 4.5 mm
2.54 mm-pitch clamp terminal
(recommended tightening torque: 0.12 – 0.15 N·m)
Applicable wires: 0.14 to 0.5 mm2 (AWG26 to AWG20)
Stripped wire length: 4.5 mm
Communication
standard
Transmission type
Rate
Connector type
Segment
Protocol
2 (M3 screw terminal)
Current output: 4 to 20 mA DC or 0 to 20 mA DC
600 Ω or less
±0.1% of span (±5% of span for 1 mA or less) The accuracy is that in the standard operating conditions: 23±2°C,
55±10%RH.
±0.02% of F.S./°C or less
Number of inputs
Input type
12 to 24 V DC (10.2 to 26.4 V DC) 20 mA or more
● Ethernet Communication
● Analog Output (AO)
Effect of ambient
temperature
0.6 V DC or less
0.1 mA or less
▌ Communication Specifications
*1: With digital filter set
Number of outputs
Output type
Load resistance
Output accuracy
12 (Note : DO12 is used for DO12 and FAIL output.)
Transistor contact output (SINK: Share a common wire with the external
power supply)
Photo-coupler isolation (internal circuit – input)
Lower than the external power supply voltage
100 mA / one DO
I
2
O
±30 V DC max.
1500 V (*)
* This is a reference safety value. This value is not necessarily a guarantee of instrument
performance.
CE marking
EMC Directive
EN61326-1 Class A, Table2
EN61326-2-3
EN55011 Class A Group1
* The instrument continues to operate at a measurement accuracy of within ±10% of the range during testing.
EMC Regulatory Arrangement in Australia and New Zealand
EN55011 Class A Group1
KC marking
Electromagnetic wave interference prevention standard, electromagnetic wave
protection standard compliance External Dimensions.
● Environmental resistance
Compliant with RoHS, WEEE
IM 25G10B01-01EN page 2/4