Download Advantage21 Programming Manual

Transcript
Fault Management Parameters
Code
Name/Description
M Undervoltage Fault Operation Mode
F627
0
1
2
Adjustment range
Factory setting
-
0
v Alarm only (detection level below 60 %)
If parameter F627 is set to 0 and the supply voltage drops below 60% of its rated value, the drive will stop and
indicate a fault code on the graphic display terminal, but it will not activate a fault relay. If the supply voltage rises
above 60% of its rated value, the fault code on the graphic display terminal will be cleared without a fault reset
action and the drive will be ready to operate.
v Fault (detection level below 60 %)
If parameter F627 is set to 1 and the supply voltage drops below 60% of its rated value, the drive will fault and
will require a reset action to clear the fault before it can be restarted.
v Alarm only (detection level below 50 %)
If parameter F627 is set to 2 and the supply voltage drops below 50% of its rated value, the drive will stop and
indicate a fault code on the graphic display terminal, but it will not activate a fault relay. If the supply voltage rises
above 50% of its rated value, the fault code on the graphic display terminal will be cleared without a fault reset
action and the drive will be ready to operate.
The use of a line reactor is required if parameter F267 is set to 2.
M Overvoltage Fault Protection
F305
0
-
2
v Enabled
If parameter F305 is set to 0, and the drive detects an impending DC bus overvoltage fault, it will automatically
take one of the following actions:
- Increase the deceleration time
- Keep the motor at a steady speed
- Increase the motor speed
Output
Frequency
DC Bus Voltage
1
2
3
: Over-Voltage
Fault Operation Leve
v Disabled
If parameter F305 is set to 1, the drive will take no action to avoid a DC bus overvoltage fault.
v Enabled (quick deceleration mode)
If parameter F305 is set to 2, and the drive detects an impending DC bus overvoltage fault, it will increase the
V/Hz ratio of the power applied to the motor. Motor over-excitation is used to dissipate regenerative energy into
the motor instead of the drive.
v Enabled (dynamic quick deceleration mode)
If parameter F305 is set to 3, the drive will increase the V/Hz ratio of the power applied to the motor as soon as
slow down begins instead of waiting for the DC bus voltage to approach the fault level.
When motor speed is being reduced, a DC bus overvoltage fault can often be caused by regenerated energy being
absorbed by the drive from the load and motor.
F626
M Overvoltage Fault Operation Level
100 to 150 % of
nominal DC bus
voltage
140 %
Parameter F626 sets the DC bus voltage level at which the actions defined by parameter F305 take place.
See diagram above for more details.
AAV75193 09/20009
101