Fault Management Parameters Code Name/Description M Undervoltage Fault Operation Mode F627 0 1 2 Adjustment range Factory setting - 0 v Alarm only (detection level below 60 %) If parameter F627 is set to 0 and the supply voltage drops below 60% of its rated value, the drive will stop and indicate a fault code on the graphic display terminal, but it will not activate a fault relay. If the supply voltage rises above 60% of its rated value, the fault code on the graphic display terminal will be cleared without a fault reset action and the drive will be ready to operate. v Fault (detection level below 60 %) If parameter F627 is set to 1 and the supply voltage drops below 60% of its rated value, the drive will fault and will require a reset action to clear the fault before it can be restarted. v Alarm only (detection level below 50 %) If parameter F627 is set to 2 and the supply voltage drops below 50% of its rated value, the drive will stop and indicate a fault code on the graphic display terminal, but it will not activate a fault relay. If the supply voltage rises above 50% of its rated value, the fault code on the graphic display terminal will be cleared without a fault reset action and the drive will be ready to operate. The use of a line reactor is required if parameter F267 is set to 2. M Overvoltage Fault Protection F305 0 - 2 v Enabled If parameter F305 is set to 0, and the drive detects an impending DC bus overvoltage fault, it will automatically take one of the following actions: - Increase the deceleration time - Keep the motor at a steady speed - Increase the motor speed Output Frequency DC Bus Voltage 1 2 3 : Over-Voltage Fault Operation Leve v Disabled If parameter F305 is set to 1, the drive will take no action to avoid a DC bus overvoltage fault. v Enabled (quick deceleration mode) If parameter F305 is set to 2, and the drive detects an impending DC bus overvoltage fault, it will increase the V/Hz ratio of the power applied to the motor. Motor over-excitation is used to dissipate regenerative energy into the motor instead of the drive. v Enabled (dynamic quick deceleration mode) If parameter F305 is set to 3, the drive will increase the V/Hz ratio of the power applied to the motor as soon as slow down begins instead of waiting for the DC bus voltage to approach the fault level. When motor speed is being reduced, a DC bus overvoltage fault can often be caused by regenerated energy being absorbed by the drive from the load and motor. F626 M Overvoltage Fault Operation Level 100 to 150 % of nominal DC bus voltage 140 % Parameter F626 sets the DC bus voltage level at which the actions defined by parameter F305 take place. See diagram above for more details. AAV75193 09/20009 101