Download Code Alarm F60 Installation manual
Transcript
Overview PID control PO R/L1 S/L2 T/L3 PA/+ PC/- RUN U/T1 V/T2 W/T3 % PRG MON Loc Rem FLC FLB MODE F ENT R RUN STOP Feedback transmitter PLC RYA RYC PLC P RES FLA Sink M Hz P24 FM I U Source FM SW101 SW102 CC Term SW103 I VIA U VIB U PTC SW100 B A GND SCR PP VIA VIB CC Setpoint 0 - 10 V Feedback mA or voltage signal 1. Wire analog inputs as indicated in the above figure. 2. Set switch SW102 to source. 3. If the feedback is a milliamp signal, set switch SW100 to the I (current) position. If the feedback is a voltage signal, set switch SW100 to the V (voltage) position. 4. Program common parameters of ATV212 (see Quick Menu page 55). 5. Program specific parameters for PID control as indicated in the following table: Parameter FMOd [Frequency mode sel] F109 [VIA selection] F200 [Auto/man speed ref] F360 [PID control enable] F359 [PID ctrl wait time] F362 [PID Prop Gain] F363 [PID Integral Gain] F366 [PID Derivative Gain] F380 [PID reverse error] F391 [Stop on LL hyst] F392 [PID wake up (thres)] F393 [PID wake up, feedb] 44 Page 77 90 108 110 111 110 110 111 111 111 111 111 Setting 2 [Communication] Factory value 1 0 [AI] 0 0 [Enable] 0 1 [PID by VIA] 0 0s 0.30 % In accordance with the application 0.20 0.00 0 0.2 Hz 0.0 Hz 0.0 Hz S1A53838 09/2011