novaPLC 2.0 19 Appendix J: Compiler Errors and Warnings 19.2.1.311 4402 "Direct access only allowed on I/Os." Make sure that you only access variables which are defined as input or output. 19.2.1.312 4403 "STEP5/7 instruction invalid or not convertible to IEC 61131-3." Some STEP5/7 commands are not convertible to IEC 61131-3, e.g. CPU commands like MAS. 19.2.1.313 4404 "STEP5/7 operand invalid or not convertible to IEC 61131-3." Some STEP5/7 operands are not convertible to IEC 61131-3 respectively an operand is missing. 19.2.1.314 4405 "Reset of a STEP5/7 timer cannot be converted into IEC 61131-3." The corresponding IEC timer have no reset input. 19.2.1.315 4406 "STEP5/7 Counter constant out of range (max. 999)." There is no valid BCD coded counter constant in the accu. 19.2.1.316 4407 "STEP5 instruction not convertible to IEC 61131-3." Some STEP5/7 instructions cannot be converted to IEC 61131-3, e.g. DUF. 19.2.1.317 4408 "Bit access of timer or counter words not convertible into IEC 61131-3." Special timer/counter commands are not convertible into IEC 61131-3. 596 7001066003 S1 Sauter Systems