Download Siemens MICROMASTER Operating instructions
Transcript
04/02 1 Parameters P0320 Motor magnetizing current CStat: CT P-Group: MOTOR Datatype: Float Active: Immediately Unit: % QuickComm. Yes Min: Def: Max: 0.0 0.0 99.0 Level: 3 Defines motor magnetization current in [%] relative to P0305 (rated motor current). Dependency: P0320 = 0: Setting 0 causes calculation by P0340 = 1 (data entered from rating plate) or by P3900 = 1 - 3 (end of quick commissioning). The calculated value is displayed in parameter r0331. Level: r0330 Rated motor slip Min: Datatype: Float Unit: % Def: P-Group: MOTOR Max: - 3 Displays nominal motor slip in [%] relative to P0310 (rated motor frequency) and P0311 (rated motor speed). r0330 [%] = r0331 P0311 ⋅ r0313 60 ⋅ 100 % P0310 P0310 − Rated magnetization current Datatype: Float Min: Def: Max: - Level: Unit: A Min: Def: Max: - Level: Unit: - P-Group: MOTOR 3 Displays calculated magnetizing current of motor in [A]. r0332 Rated power factor Datatype: Float P-Group: MOTOR 3 Displays power factor for motor Dependency: Value is calculated internally if P0308 (rated motor cosPhi) set to 0; otherwise, value entered in P0308 is displayed. Level: P0335 Motor cooling Min: 0 CStat: CT Datatype: U16 Unit: Def: 0 P-Group: MOTOR Active: first confirm QuickComm. Yes Max: 1 2 Selects motor cooling system used. Possible Settings: 0 Self-cooled: Using shaft mounted fan attached to motor 1 Force-cooled: Using separately powered cooling fan Notice: Motors of series 1LA1 and 1LA8 have an internal fan. This internal motor fan must not be confused with the fan at the end of the motor shaft. Level: P0340 Calculation of motor parameters Min: 0 CStat: CT Datatype: U16 Unit: Def: 0 P-Group: MOTOR Active: first confirm QuickComm. No Max: 1 2 Calculates various motor parameters, including: P0344 Motor weight P0346 Magnetization time P0347 Demagnetization time P0350 Stator resistance P0611 Motor I2t time constant P1253 Vdc-controller output limitation P1316 Boost end frequency P2000 Reference frequency P2002 Reference current Possible Settings: 0 No calculation 1 Complete parameterization Note: This parameter is required during commissioning to optimize inverter performance. P0344 Motor weight CStat: CUT P-Group: MOTOR Datatype: Float Active: Immediately Unit: kg QuickComm. No Min: Def: Max: 1.0 9.4 6500.0 Level: 3 Specifies motor weight [kg]. Note: This value is used in the motor thermal model. It is normally calculated automatically from P0340 (motor parameters) but can also be entered manually. Default value is dependant on inverter rated power. MICROMASTER 420 Parameter List 6SE6400-5BA00-0BP0 27