TempTracker mod+ Hybrid Installation and Operation Manual
39
Boiler Stage Menu
OD=
55oFSYS=143oF
<<A>>
67%
STAGE ◄ ►
Staging
STAGE A SETTINGS
Mode
Auto
<Prev Stage>
<Next Stage>
BACK ▲ ▼ SELECT
STAGE A MODE
Auto
Standby
Manual
Off
On
BACK ▲ ▼ SAVE
B
20%
MENU
Modulation
STAGE A SETTINGS
Mode
Auto
Ignition %
1%
Mod Start %
80%
<Prev Stage>
<Next Stage>
Copy Settings
BACK ▲ ▼ SELECT
[
STAGE A
IGNITION POINT
-
1%
]
BACK ▲ ▼ SAVE
STAGE A
MODULATION START
[
75%
]
BACK ▲ ▼ SAVE
Boiler Status
The TempTracker mod+ Hybrid boiler status gives immediate access to each boiler stages or modulation.
•---Boiler is off due to no call for heat.
•<<A>>A is the lead boiler in the lead Hybrid group. See "Lead Stages" on page 34.
•<C>C is the lead boiler in the lag Hybrid group or the lead boiler in Staging or Modulating Boiler Type. See "Lead
Stages" on page 34.
•C/EExtension panel is NOT communicating back to the TempTracker mod+ Hybrid. See "Connecting to the Extensions
and 4-20mA EMS Interface" on page 16.
•mONAll boiler stages are set to ON.
•mOFFAll boiler stages are set to OFF.
Display Modulating Boiler Status
•97%Boiler is modulating at the indicated percentage.
•m95%Boiler Stage Mode is set to Manual Modulation to the specified percent. See "Mode" on page 41.
•h50%Boiler is in post purge for 30 seconds.
Display Staging Boiler Status
HTC# 059105-00D
•HighBoiler highest firing stage is active. The boiler Mode is set to either Auto or Standby.
•MedBoiler Middle stage on a 3-stage boiler is active. The boiler Mode is set to either Auto or Standby.
•MhighBoiler Middle High stage on a 4-stage boiler is active. The boiler Mode is set to either Auto or Standby.
•MlowBoiler Middle Low stage on a 4-stage boiler is active. The boiler Mode is set to either Auto or Standby.
•LowBoiler lowest firing stage is active. The boiler Mode is set to either Auto or Standby.