Transcript
Optidrive ODV-2 User Guide Revision 1.00 Optidrive HVAC Start Up Guide OPTIDRIVE HVAC (Frame Sizes 4 to 7). Mechanical Mounting Information can be found on page 9, section 3.5. HVAC Display (Status, Diagnostics, and Programming) Keypad Operation can be found on page 13, section 5.1 Control Terminal Configuration based on factory settings Safe Torque Off (STO) Link the terminals as shown above through the emergency stop circuit contacts Supply Voltage Run / Stop 10K Pot Close the switch to run (enable) Open the switch to stop Motor Cable For correct cable size, see Technical Data on page 34, section 11.4. Observe the maximum permissible motor cable length. For Motor cable lengths > 50 metres, an output filter is recommended. Use a screened (shielded cable). The shield should be bonded to earth at both ends. Fuses or MCB Check Drive Rating info on Page 34, section 11.4 PE L1 L2 L3 AC Supply Connection 200 – 240 Volts + / - 10% 380 – 380 Volts + / - 10% Check Drive Rating info on Page 34, section 11.2 2 M www.invertek.co.uk Motor Connection Check for Star or Delta Connection. Enter the Motor Nameplate Data into the drive Parameters as follows: Motor Rated Voltage: P1-07 Motor Rated Current: P1-08 Motor Rated Frequency: P1-09 Motor Rated Speed (Optional): P1-10