Download USER MANUAL
Transcript
Section-5 4. Check if the LED LINE1 and battery is green. If yes, mains voltage is OK; On the LCD: “LOAD OFF, SUPPLY FAILURE” will appear and the LED-indicator will indicate as shown below: LED Indicator LINE 1 LINE 2 BYPASS INVERTER BATTERY Colour Green OFF OFF OFF Flashing Green 5. Make sure the bypass fuses F2 are inserted (front of Module); 6. Close internal and external battery fuses/breaker (if available); 7. Press simultaneously both “ON/OFF” Buttons to start-up UPS. LCD panel must display: “LOAD DISCONNECTED PARALLEL SWITCH OPEN” and the LEDindicator will appear as shown below: LED Indicator LINE 1 LINE 2 BYPASS INVERTER BATTERY Colour Green Green OFF Green Green 8. Transfer load to mains and inverter for testing using submenu COMMANDS 9. Transfer Load to Bypass-Mode by means of COMMAND “LOAD TO BYPASS” 10. Verify the status (Load on Bypass, Eco-Mode) by checking the LED-indicators as shown below: LED Indicator LINE 1 LINE 2 BYPASS INVERTER BATTERY Colour Green Green Green OFF Green 11. Close Parallel Isolator (IA2); 12. Open Maintenance Bypass (IA1) by turning it to position “OFF”. The load is now supplied by the static bypass. 13. Transfer load to Inverter-Mode by means of COMMAND “LOAD TO INVERTER”. On LCD: “LOAD PROTECTED” will appear. THE LOAD IS NOW PROTECTED BY THE PMC NRG VALUENET DPA USER MANUAL Page 10/16 Modifications reserved