Option Panel Operating Instructions
Terminal functions are programmed in parameter group 5** Digital In/Out. (See Table 6.2 for factory default
parameter settings for drives with an ECB). Bypass
functions are programmed in parameter group 31-**
Bypass Option (see 6.1.7 ECB Mode of Operation). See the
drive’s supporting materials for detailed programming
instructions.
Parameter
Setting title
Setting
Function
5-01 Terminal 27 Mode
Input
0
Customer Interlock
5-02 Terminal 29 Mode
Output
1
Auto bypass
5-10 Terminal 18 Digital Input
Start
8
Common run/stop
5-11 Terminal 19 Digital Input
Run Permissive
52
Run Permissive
Customer Interlock
5-12 Terminal 27 Digital Input
External Interlock
7
5-31 Terminal 29 Digital Output
No Alarm
160
Auto bypass
5-40 Function Relay (0)
Start Command Active
167
Run Permissive
5-40 Function Relay (0)
Off Delay
0.00 S
Run Permissive
6 6
Table 6.2 Parameter Group 5-** Digital In/Out Factory Default Settings