Installation
3.5
Commissioning
Checking the rotational
direction of drive and
fan motor
Attention!
Always check the rotational direction of the drive and fan motor prior to commissioning/initial start up.
Even brief operation in the wrong direction of rotation (more than approx.
5 seconds) may cause total destruction of the air end!
List up the test results in the commissioning certificate.
Caution!
Ensure that the rotational direction coincides with the rotational direction arrow on the air end.
–
Close mains disconnecting device.
–
Switch the compressor on and immediately off again to check the rotational direction.
Changing the rotational direction
Caution: Risk of injury!
Emergency stop switch/button, open mains disconnection device and secure
against unintentional switch on by means of a padlock.
Allow converter to cool off (only SLF 40 BLUEKAT).
–
Interchange two phases (L1, L2 or L3) in the power cable.
Check compressed air
outlet for tightness
Caution: Risk of injury!
Work on the compressed air system may only be carried out by experienced
and authorized qualified personnel!
Always wear protective clothing and goggles!
Immediately after having switched on the machine the connection of the
compressed air outlet must be checked for tightness!
Make sure to observe an appropriate safety distance during the inspection!
–
Close mains disconnecting device.
–
To conduct the inspection switch on the compressor and check the compressed air outlet for tightness.
–
Switch off compressor.
BOGE Operating instructions for screw compressors series SLF 30...SLF 125