Fundamentals of refrigeration
Si-18
1.3.5 Sensible heat and latent heat
At Point B, the R410A refrigerant of 0.1MPa boils at a
temperature of -51.6°C.
Therefore, at Point D, if the R410A refrigerant having a
temperature of 35°C is in a state of saturated vapor at the
pressure of 2.12MPa, it becomes refrigerant saturated liquid of
35°C by removing the condensation latent heat from the said
saturated vapor.
By contrast, at Point C, that means it is required to reduce the
pressure down to 0.94MPa in order to boil the R410A refrigerant
at 5°C.
Fig. 1-34 shows the "temperatue-heat content diagram" for 1kg
of water heated from -50°C to 150°C vapor under the
atmospheric pressure.
(1) From A to B, 105.4kJ(25.2kcal) of heat were added to
increase ice temperature from-50°C to 0°C.
(2) From B to C, 333.2kJ(79.6kcal) were added to melt ice
without changing its temperature.
(3) From C to D, 418.6kJ(100kcal) were added to heat water to
boiling point. (from 0°C to 100°C)
(4) From D to E, 2256kJ(539kcal) were added to change water
to vapor without changing its temperature.
(5) From E to F, 92.5kJ(22.1kcal) were added to increase vapor
temperature from 100°C to 150°C.
In this example,
2 The heat which was required to increase the ice temperature
is called "sensible heat". (A to B)
2 The heat which was required to change the ice to water is
called "latent heat of melting". (B to C)
2 The heat which was required to increase the water
temperature is also called "sensible heat". (C to D)
2 The heat which was required to change the water to steam is
called "latent heat of vaporization". (D to E)
If the process is reversed,
2 The heat which must be rejected to change the steam to
water is called "latent heat of condensation". (E to D)
2 The heat which must be rejected to decrease the water
temperature is called "sensible heat". (D to C)
2 The heat which must be rejected to change the water to ice is
called "latent heat of solidification". (C to B)
2 The heat which must be rejected to decrease the ice
Fig.1-33
Saturated curve of R410A and Water
MPa
2.2
MPaG
2.1
D
2.12
2.0
1.9
1.8
1.7
1.6
1.5
Liquid
Gas
1.4
1.3
R410A
1.2
1.1
(Liquid)
Condensation
Vapor (Gas)
1.0
0.9
0.94
0.8
0.6
0.7
Liquid
Evaporation
temperature is called "sensible heat". (B to A)
0.5
Fig.1-34
0.4
0.3
Water
0.2
0.1
5
35
B
0
-40 -20
-51.6
0
20
40
60
A
0.1
0
-760mHg -0.1
80 100 120
Temperature (ºC)
mmHg
18