Download Case Model - Service.daikin.com
Transcript
Fundamentals of refrigeration Si-18 1.3.5 Sensible heat and latent heat At Point B, the R410A refrigerant of 0.1MPa boils at a temperature of -51.6°C. Therefore, at Point D, if the R410A refrigerant having a temperature of 35°C is in a state of saturated vapor at the pressure of 2.12MPa, it becomes refrigerant saturated liquid of 35°C by removing the condensation latent heat from the said saturated vapor. By contrast, at Point C, that means it is required to reduce the pressure down to 0.94MPa in order to boil the R410A refrigerant at 5°C. Fig. 1-34 shows the "temperatue-heat content diagram" for 1kg of water heated from -50°C to 150°C vapor under the atmospheric pressure. (1) From A to B, 105.4kJ(25.2kcal) of heat were added to increase ice temperature from-50°C to 0°C. (2) From B to C, 333.2kJ(79.6kcal) were added to melt ice without changing its temperature. (3) From C to D, 418.6kJ(100kcal) were added to heat water to boiling point. (from 0°C to 100°C) (4) From D to E, 2256kJ(539kcal) were added to change water to vapor without changing its temperature. (5) From E to F, 92.5kJ(22.1kcal) were added to increase vapor temperature from 100°C to 150°C. In this example, 2 The heat which was required to increase the ice temperature is called "sensible heat". (A to B) 2 The heat which was required to change the ice to water is called "latent heat of melting". (B to C) 2 The heat which was required to increase the water temperature is also called "sensible heat". (C to D) 2 The heat which was required to change the water to steam is called "latent heat of vaporization". (D to E) If the process is reversed, 2 The heat which must be rejected to change the steam to water is called "latent heat of condensation". (E to D) 2 The heat which must be rejected to decrease the water temperature is called "sensible heat". (D to C) 2 The heat which must be rejected to change the water to ice is called "latent heat of solidification". (C to B) 2 The heat which must be rejected to decrease the ice Fig.1-33 Saturated curve of R410A and Water MPa 2.2 MPaG 2.1 D 2.12 2.0 1.9 1.8 1.7 1.6 1.5 Liquid Gas 1.4 1.3 R410A 1.2 1.1 (Liquid) Condensation Vapor (Gas) 1.0 0.9 0.94 0.8 0.6 0.7 Liquid Evaporation temperature is called "sensible heat". (B to A) 0.5 Fig.1-34 0.4 0.3 Water 0.2 0.1 5 35 B 0 -40 -20 -51.6 0 20 40 60 A 0.1 0 -760mHg -0.1 80 100 120 Temperature (ºC) mmHg 18