Section 11 Secondary system supervision 1MRK 502 042-UUS A GUID-B056E9DB-E3E5-4300-9150-45916F485CA7 V1 EN Figure 95: Operating principle of the trip-circuit supervision with an external resistor. The TCSSCBR blocking switch is not required since the external resistor is used. If the TCSSCBR is required only in a closed position, the external shunt resistance may be omitted. When the circuit breaker is in the open position, the TCSSCBR sees the situation as a faulty circuit. One way to avoid TCSSCBR operation in this situation would be to block the monitoring function whenever the circuit breaker is open. 255 Application Manual