Section 13
Logic
1MRK 502 042-UUS A
13.1.3
Setting guidelines
The parameters for Tripping logic common 3-phase output SMPPTRC (94) are set via
the local HMI or through the Protection and Control Manager (PCM600).
The following trip parameters can be set to regulate tripping.
Operation: Sets the mode of operation. Disabled switches the function off. The normal
selection is Enabled.
TripLockout: Sets the scheme for lock-out. Disabled only activates the lock-out output.
Enabled activates the lock-out output and latches the output TRIP. The normal
selection is Disabled.
AutoLock: Sets the scheme for lock-out. Disabled only activates lock-out through the
input SETLKOUT. Enabled additonally allows activation through the trip function
itself. The normal selection is Disabled.
tTripMin: Sets the required minimum duration of the trip pulse. It should be set to
ensure that the breaker is tripped correctly. Normal setting is 0.150s.
13.2
Trip matrix logic TMAGGIO
13.2.1
Identification
Function description
Trip matrix logic
13.2.2
IEC 61850
identification
TMAGGIO
IEC 60617
identification
-
ANSI/IEEE C37.2
device number
-
Application
The Trip matrix logic TMAGGIO function is used to route trip signals and other
logical output signals to the tripping logics SMPPTRC and SPTPTRC or to different
output contacts on the IED.
TMAGGIO output signals and the physical outputs allows the user to adapt the signals
to the physical tripping outputs according to the specific application needs.
13.2.3
Setting guidelines
Operation: Turns the operation of the function Enabled/Disabled.
293
Application Manual