Download 3 When
Transcript
Check code name Check code name [H02] / [1d] Compressor error (Lock) Cause of operation 1. 2. 3. 4. 5. (d07 / AI-NET) Outdoor unit power line error Compressor circuit system error Compressor error Refrigerant stagnation in compressor shell IPDU P.C. board error Sub-code: 01: Compressor 1 side 02: Compressor 2 side NO Is power voltage of outdoor unit normal? *1 *1 380–415V ± 10% YES Does voltage drop occur when other compressor starts? YES Correct power line. NO YES Does OCR of MG-SW operate? Reset OCR manually. *3 NO Is wiring or connector connection on IPDU P.C. board normal? NO Correct connector connection or wiring. YES YES Is not it an abnormal overload? Correct cause of overload. NO Is there no refrigerant stagnation in compressor shell? YES Is case heater output normal? YES Correct refrigerant stagnation in compressor shell. NO NO Operation starts. Check case heater. Is compressor normal? *2 NO Compressor error YES Check IPDU P.C. board. *2 Check the following items mainly. 1. Existence of abnormal sound and abnormal vibration during operation or starting 2. Abnormal overheat of case during operation or stop time (Never touch with hands.) 3. Current of compressor lead during operation or starting time (No varied change of current) change *3 If OCR operates even after manual reset of OCR, check whether the wiring to the current sensor (TO2) of Comp-IPDU is correct or not. 171