Download 3 When
Transcript
17-2-7. Notice for Wiring Wiring for service shall be done according to the wiring diagram. Special caution is needed for reactor, which has different connecting points on COMP-IPDU1 and COMPIPDU2. COMP-IPDU No.1 COMP-IPDU No.2 TO REACTOR 1 TO REACTOR 2 CN20 (REACTOR 1) CN21 (REACTOR 1) CN08 (REACTOR 2) CN07 (REACTOR 2) P.C. board noise P.C. filter board P.C. board interface power P.C. board P.C. board Comp-IPDU Comp-IPDU No.1 No.2 Inverter front view DANGER The electrolytic capacitors in this panel are charged to 660 volts D.C. Before servicing, turn off the power supply and allow the capacitor to discharge for at least 10 minutes. (Purpose: Discharge the capacitor) Discharge to a safe level 10 volts D.C. or LESS. Test with a D.C. Voltmeter as shown. CN13 (CAPA–) CN15 (CAPA+) 10V, DC Comp-IPDU No.1 & No.2 COMP-IPDU No. 1 and COMP-IPDU No.2 have the same electric potential, but both voltages shall be measured. Never discharge the capacitor terminals with any metal implement. Personal injury or equipment damage may result. 268