CHAPTER 4 CONTROLLER
Diagnosis
Attachment 2A Solenoid Warning (F65)
Logic conditions
· CAN receiving of abnormal flag from output
unit.
Recovery
Turn ON power again.
Action
· Set Attachment 2 current command value to 0 mA.
LED blink pattern
E
Diagnosis
Attachment 2B Solenoid Warning (F67)
Logic conditions
· CAN receiving of abnormal flag from output
unit.
Recovery
Turn ON power again.
Action
· Set Attachment 2 current command value to 0 mA.
LED blink pattern
E
Diagnosis
Attachment 2 Solenoid Leak (F69)
Logic conditions
· CAN receiving of abnormal flag from output
unit.
Recovery
Turn ON power again.
Action
· Set the current command value of all operating functions to 0 mA and turn OFF unload solenoid.
LED blink pattern
E
Diagnosis
Attachment 3A Solenoid Warning (F70)
Logic conditions
· CAN receiving of abnormal flag from output
unit.
Recovery
Turn ON power again.
Action
· Set Attachment 3 current command value to 0 mA.
LED blink pattern
E
Diagnosis
Attachment 3B Solenoid Warning (F72)
Logic conditions
· CAN receiving of abnormal flag from output
unit.
Recovery
Turn ON power again.
Action
· Set Attachment 3 current command value to 0 mA.
LED blink pattern
E
Diagnosis
Hour meter GAP warning (F73)
Logic conditions
· Hour meter difference between meter panel
and VCM-6 is ± 24 hours or more.
Recovery
Update #252 M/P hour meter with service tool.
Action
· VCM-6 sends zero to hour meter.
· VCM-6 hour meter is not overwritten.
LED blink pattern
E
F65
F67
F69
F70
F72
F73