Download High Performance Model QCPU(Q Mode)User`s Manual(Function

Transcript
14 SYSTEM CONFIGURATION OF MULTIPLE CPU SYSTEM
MELSEC-Q
14.2.2 Precautions when using Q Series I/O modules and intelligent function modules
(1) Compatible I/O modules
All I/O modules (QX , QY ) are compatible with to multiple CPU system.
They can be used by setting any of CPU No.1 to No.4 as a control CPU.
(2) Compatible intelligent function modules
(a)
The intelligent function modules compatible with the multiple CPU system
are those of function version B or later. They can be used by setting any of
CPU No.1 to No.4 as a control CPU.
(b)
Q Series high speed count modules (QD62, QD62D, QD62E) are
compatible with by multiple CPU system are those of function version A or
later. They can be used by setting any of CPU No.1 to No.4 as a control
CPU.
(c)
Q Series interruption modules (QI60) do not have a function version, but are
supported by multiple CPU system. CPUs No.1 to No.4 can be set up as
control CPUs.
(d)
Intelligent function modules of function version A can be used in multiple
CPU system by setting CPU No.1 as a control CPU.
However, only control CPU can be accessed from serial communication
modules and other external modules. (MELSECNET/H, serial
communication modules and other external modules cannot access noncontrol CPUs.)
The "SP. UNIT VER. ERR (error code: 2150)" occurs if any of CPU No.2 to
No.4 has been set as a control CPU, and the multiple CPU system will not
be a started up.
(3) Ranges of access to control and non-control modules
In a multiple CPU system, non-control modules can be accessed by setting "I/O
setting outside of the group" at the "Multiple CPU settings" dialog box in "PLC
Parameter". The following table indicates accessibility to the control and noncontrol modules in the multiple CPU system.
Accessibility
Access target
Control module
Non-control module (I/O setting outside of the group)
Disabled
Enabled
Input (X)
Output (Y)
Buffer
memory
Read
Write
Read
Write
: Accessible
: Inaccessible
REMARK
• The function version of intelligent function modules can be confirmed at the rated
name plate of the intelligent function module and with the GX Developer's "System
monitor product information list window" (see Section 2.3.)
• See Section 14.2.4 for details on restrictions on the number that can be used with
intelligent function modules.
14 - 9
14 - 9