Technical specifications of the pRack PR100 Compact board
Analogue inputs
Analogue conversion
Maximum number
Type
Time constant
Input precision
Classification of the measurement circuits
10-bit A/D converter embedded in CPU
8
Universal: 2 (inputs B1, B2)
- CAREL NTC (-50T90°C; R/T 10 kΩ±1% at 25°C), NTC HT0T150 °C
- Voltage 0 to 1 Vdc, 0…10 Vdc, 0 to 5 Vdc ratiometric
- Current 0…20 mA or 4…20 mA. Input Resistance: 100 Ω
Universal: 2 (inputs B3, B4)
- CAREL NTC (-50T90°C; R/T 10 kΩ±1% at 25°C) NTC HT0T150 °C
- Voltage 0 to 1 Vdc
- PT1000 (-100T200 °C; R/T 1000 Ω at 0°C)
Universal: 2 (inputs B5, B6)
- CAREL NTC (-50T90°C; R/T 10 kΩ±1% at 25°C) NTC HT0T150 °C
- Voltage 0 to 1 Vdc, 0…10 Vdc, 0 to 5 Vdc ratiometric
- Voltage-free digital inputs, 5 mA
Passive: 2 (inputs B7, B8)
-CAREL NTC (-50T90°C; R/T 10kΩ±1% at 25°C) NTC HT0T150 °C
- Voltage-free digital inputs, 5 mA
Selectable via software
0,5 s
± 0.3 % of full scale
Category 1 (IEC EN 61010-1)
Tab. 2.b
Important: the 21 Vdc available at terminal +VDC (J2) can be used to power any active probes. The maximum current is Imax=60 mA, thermally
protected against short-circuits. To power the 0 to 5 Vdc ratiometric probes, use the 5V available at terminal +5Vref (J2). The maximum current is
Imax=60 mA, thermally protected against short-circuits.
Digital inputs
Type
Maximum number
Minimum digital input impulse detection time
Power supply
Not optically-isolated, voltage-free contact
6: 2 + 4 multifunction analogue inputs
Normally open (open-closed-open)
Normally closed (closed-open-closed)
internal
250 ms
250 ms
Tab. 2.c
Analogue outputs
Type
Maximum number
Power supply
Precision
Resolution
Settling time
Maximum load
Not optically-isolated
2: 1 PWM phase control output (Y1) with 5V pulse of programmable duration and 1 x 0 to 10 Vdc output (Y2)
internal
± 2% of full scale on Y2
8 bit
2 s on Y2
1 k (10 mA) for 0…10 Vdc and 470  (10 mA) for PWM
Tab. 2.d
Note: the synchronicity for the PWM phase control output is taken from the SYNC input and G0 (J2).
Digital outputs
Important: The outputs can be divided into groups, depending on the insulation distance. The relays belonging to the same group have basic
insulation between each other and therefore must have the same power supply (24 Vac or 110 to 230 Vac). Between groups there is double insulation
and consequently these may have different voltages.
Models PRK100X*A* & PRK100X*B*
Makeup of the groups
Type of relay Group 1 (J3)
Type A Available with NC and
NO contacts
Features
MOSFET photovoltaic relay
Operating voltage 24 Vac/Vdc
Maximum power 10 W
Maximum number
No. of changeover contacts
Number of SSR outputs
Group 2 (J10)
Group 3 (J11)
Type A Available with NO
contacts
Type B Available with NO contacts
SPST, 1250 VA, 250 Vac, 5 A resistive.
UL873: 1 A resistive, 1 A FLA, 6 A LRA, 250 Vac,
D300 pilot duty (30.000 cycles).
EN 60730-1: 1 A resistive, 1 A inductive, cosφ=0.6, 1(1) A
(100.000 cycles)
7
None
2: outputs NO1 and NO2 (J3 and J10)
Tab. 2.e
11