16: INTERFACE INSTRUCTIONS DGRD (Digital Read) DGRD BCD4 When input is on, data designated by operands I and Q is set to a data register designated by destination operand D1. I Q D1 ***** ***** ***** This instruction can be used to change preset values for timer and counter instructions using digital switches. The data that can be read using this instruction is 0 through 65535 (5 digits), or FFFFh. First output number First input number Quantity of digits: 1 to 5 (decimal) 1 to 4 (hex) Conversion: BCD or BIN Applicable CPU Modules FC4A-C10R2/C FC4A-C16R2/C FC4A-C24R2/C FC4A-D20K3/S3 FC4A-D20RK1/RS1 & FC4A-D40K3/S3 — — X X X Note: The DGRD instruction requires transistor output terminals. When using all-in-one 24-I/O type CPU module FC4A-C24R2 or FC4A-C24R2C, connect a transistor output module. Valid Operands Operand Function I Q I Q D1 (Destination 1) M R T C D First input number to read X — — — — — — — — First output number for digit selection — X — — Destination to store results — — — — — — — — — — — — — X Constant Repeat For the valid operand number range, see pages 6-1 and 6-2. The DGRD instruction can read 65535 (5 digits) at the maximum. When the read value exceeds 65535 with the quantity of digits set to 5, a user program execution error will result, turning on special internal relay M8004 and the ERR LED. Note: The DGRD instruction can be used up to 16 times in a user program. When transferring a user program containing more than 16 DGRD instructions to the CPU, a user program syntax error occurs, turning on the ERR LED. The user program cannot be executed. Conversion BCD: BIN: To connect BCD (decimal) digital switches To connect BIN (hexadecimal) digital switches Input Points Inputs are used to read the data from digital switches. The quantity of required input points is always 4. Four input points must be reserved starting with the input number designated by operand I. For example, when input I0 is designated as operand I, inputs I0 through I3 are used. Output Points Outputs are used to select the digits to read. The quantity of required output points is equal to the quantity of digits to read. When connecting the maximum of 5 digital switches, 5 output points must be reserved starting with the output number designated by operand Q. For example, when output Q0 is designated as operand Q to read 3 digits, outputs Q0 through Q2 are used. Digital Switch Data Reading Time Reading digital switch data requires the following time after the input to the DGRD instruction is turned on. Keep the input to the DGRD instruction for the period of time shown below to read the digital switch data. For example, when reading data from 5 digital switches to the destination operand, 14 scans are required Digital Switch Data Reading Time 2 scan times × (Quantity of digits + 2) « MICROSMART USER’S MANUAL » 16-3
Related documents
G2A user guideV11.2.2
IDEC MicroSmart Pentra PLC User`s Manual
Programmable Logic Controllers
"user manual"
MicroSmart Pentra PLC Logic Controllers
Specifications - Idec Elektrotechnik GmbH
Complete PLC Catalog
(FC4A) Series PLCs
opennet controller - Steven Engineering
IDEC MicroSmart User Manual
"user manual"
IDEC ONC Series OpenNet Controller User`s Manual