7 - Programmed Setpoint
7.5.3 DIGITAL INPUT COMMANDS FOR SETPOINT PROGRAMMER FUNCTION (OPTION)
Function
None
Set manual mode
Keyboard lock
PV measure hold
Setpoint slopes inhibition
Output forcing
1st Program selection
2nd Program selection
3rd Program selection
4th Program selection
Program Start/Hold
Program reset
Deactivation of blocking
Next segment
68
Performed operation
Parameter
value
O
# FF
A
# M
. an
k
# eb.I
H
# p
. U
S
# lo.1
F
# O
. ut
P
# rg.1
P
# rg.2
P
# rg.3
P
# rg.4
#r.=H.
r
# St
blck
n
# eHt
Off
On
Notes
—
—
Automatic
Manual
Unlock
Locked
Normal operation
PV is hold
Rate limiting is active
Normal operation
When the input is in the on state, the Setpoint is changed in steps
Normal operation
Forced output value
Digital input ON means activation forcing output value (see page 28)
Local
1st program
Local
2nd program
Local
3rd program
Local
4th program
HOLD
Normal operation
—
—
Not used
With the keypad locked the commands from digital inputs and
serial communications are still operating
The value of PV is “frozen” at the time the digital input goes to
the close state
Program selection by permanent closure
of the digital input
When the input is in the On state, the program is executed up
to the end. When off, the program is forced in hold.
Digital input ON means program reset and control switching to
Program reset
Local setpoint
blocking function is activated at the time the digital input
Reactivation of blocking The
goes to the close state
Skips to the next segment The program skips to the next segment of the program at the time
the digital input goes to the close state
RUN