Download TeSys
Transcript
Multifunction Control Unit 2-5-4-10-2 TripTime Parameter (line 1) TripTime Setting (line 2) = 10 Sec. Definition Use or to select the desired time. Units Sec. The Trip Time parameter is adjustable from 1 to 200 seconds in increments of 1 second. Default setting is 10 seconds. ENT : Saves setting and returns to 4_AdvSetup (page 45). ESC : Does not save a setting, returns to 4_AdvSetup (page 45). 2-5-4-10-3 TripLevel ENGLISH Parameter (line 1) TripLevel Setting (line 2) Definition = 100% FLA Use or to select the desired level. Units % FLA The Trip Level parameter is adjustable from 100 to 800% of the FLA setting in increments of 10%. Default setting is 100% FLA. ENT : Saves setting and returns to 4_AdvSetup (page 45). ESC : Does not save a setting, returns to 4_AdvSetup (page 45). 2-5-4-10-4 Warning Parameter (line 1) Warning Setting (line 2) Definition = Off Disables the Warning parameter. Disabled by default. ? On Enables the Warning parameter. ENT : Saves setting and returns to 4_AdvSetup (page 45). ESC : Does not save a setting, returns to 4_AdvSetup (page 45). 2-5-4-10-5 Warn Level Parameter (line 1) Warn Level Setting (line 2) Definition = 100% FLA Use or to select the desired level. Units % FLA The Warn Level parameter is adjustable from 100 to 800% of the FLA setting in increments of 10%. Default setting is 100% FLA. ENT : Saves setting and returns to 4_AdvSetup (page 45). ESC : Does not save a setting, returns to 4_AdvSetup (page 45). 64 Chapter 2 - Operation 05-2004