EXCEL10 HYDRONIC CONTROLLER SYSTEM ENGINEERING
APPENDIX A. USING E-VISION TO COMMISSION A HYDRONIC CONTROLLER
Temperature Sensor Calibration
the actual Measured Value. When a value is typed in
and Calibrate is clicked, the offset value is
automatically calculated, displayed, and written to the
Excel 10 Hydronic Controller.
The temperature sensor in the Excel10 wall modules can be
calibrated to correct for sensor inaccuracies, wire resistance,
etc. This allows the Excel 10 Hydronic Controller to sense the
space temperature with a high degree of accuracy.
Procedure
Select the controller being worked on with E-Vision (see the
E-Vision User Guide for details on using E-Vision
From within E-Vision, with the desired Hydronic plant loaded
and the SLTA (Q7752A) connected to the E-Bus or via the BPort of an Excel 10 Zone Manager, perform the following
procedure:
1. Select a controller symbol from a network diagram.
Fig. 20. Calibration dialog box.
NOTE: Record the offset value to be manually restored
if additional downloads are performed.
2. Click on Calibrate from the Controller menu. Once
E-Vision logs on to the controller, the Room
Temperature Calibration dialog box appears.
4. Click on Close after completing adjustments.
3. The box displays the Current Value of the sensor and
the current Offset; it also contains a field for entering