Download "user manual"
Transcript
Lighting Interior Lighting Power Example 9-M—Wall Sconces in Office Corridor Q The space-by-space method is being used to determine interior lighting compliance for an office building with 1,000 ft² of corridors that provide access to private offices. Compact fluorescent wall sconces illuminate the corridors. There is no other form of illumination in the corridors. Are the corridors eligible for an additional decorative lighting power allowance? If so, is it possible to make power trade-offs between the corridor and other spaces within the office building? A The lighting cannot be considered decorative since it is the only source of illumination for the corridors. The lighting power allowance is 0.5 W/ft² and the power used by the wall sconces must be less than this amount or a total of 500 W for all the corridors. Since the space-by-space method is being used, trade-offs can be made between the corridors and other areas of the building. Figure 9-E—Additional Allowance, Decorative Luminaires Example 9-N—Lighting Systems in Multi-Function Rooms Q The space-by-space method is being used to determine interior lighting compliance for a hotel multi-function room that measures 60 ft x 120 ft. The room has two general lighting systems: a fluorescent lighting system that is used for meetings and conferences and an incandescent lighting system that consists of recessed PAR lamps in recessed cans. Controls for the two lighting system are interlocked so that only one lighting system can be turned on at a time. In addition to the two lighting systems, the room has eight chandeliers and wall sconces located around the perimeter of the room at a spacing of 10 ft. What is the lighting power allowance for the space? A Figure 9-F—Additional Allowance, Decorative Luminaires Determining the Connected Lighting Power Once the interior lighting power allowance has been determined, it is then necessary to calculate the connected lighting power (CLP) and to show that this value is less than or equal to the allowance. Interior The basic interior lighting power allowance for the room is 1.3 W/ft², which is taken from the “Conference Meeting / Multipurpose” space category (see Table 9.6.1). Since the two lighting system have controls that prevent them both from being turned on at the same time, only the system that uses the most lighting power needs to be counted in the tabulation of connected lighting power. Since the space has chandeliers and wall sconces, it qualifies for an additional 1.0 W/ft² of lighting power; however, this additional lighting power must be used only for the decorative lighting. The compliance process requires that the lighting power be separately tabulated for each general lighting system and for the decorative lighting. The power used for decorative lighting must be less than 1.0 W/ft² or a total of 7,200 W. The power used by each general lighting system must be less than 1.3 W/ft² or a total of 9,360 W. The decorative lighting cannot be traded off against lighting in other areas of the building, but the lighting for general illumination can be used for trade-offs. --`,``,``,`,,,,,`````,`,```,```,-`-`,,`,,`,`,,`--- 9-20 Copyright ASHRAE Provided by IHS under license with ASHRAE No reproduction or networking permitted without license from IHS User’s Manual for ANSI/ASHRAE/IESNA Standard 90.1-2007 Licensee=AECOM/5906698001, User=li, xiaoxiao Not for Resale, 07/02/2009 03:02:18 MDT