Download "user manual"
Transcript
HVAC Mandatory Provisions Setback controls prevent spaces from becoming so cold, or so hot, during offhours that the HVAC system will not be able to bring them back to a comfortable range in a reasonable period of time. They save energy because if they are not present, systems in extreme climates are often programmed to run 24 hours at least part of the year to avoid under-cooled or under-heated spaces in the morning or possible damage to materials within the building. While setback controls are required to have the setpoint capabilities listed above, these setpoints may not be the optimum for all applications. For buildings that are massive, or where heating or cooling capacity is marginal, it may be more energy efficient to setback temperatures only slightly from occupied setpoints. (Radiant floor and low temperature ceiling heating systems are exempt from set back requirements for this reason; their inherently slow pickup capability makes only a slight setback possible.) The best way to determine optimum setpoints is by trial and error once the building and system installations are complete. Computer simulations are also possible but not always accurate because of the very complex ways that energy is transferred into and out of and stored within building mass. Optimum Start Controls (§ 6.4.3.1.3) The simplest time switch or scheduling controls start systems each day based on 6-24 Copyright ASHRAE Provided by IHS under license with ASHRAE No reproduction or networking permitted without license from IHS the time of day. To ensure that the space is comfortable prior to occupancy, these controls are typically scheduled to start two or three hours prior to the expected occupancy time to allow for warm-up or cool-down. But this amount of warmup/cool-down time is not always required. For instance, during mild weather, the space may be very near comfort conditions and require little or no warmup/cool-down period. To eliminate this unnecessary system operating time, optimum start controls were developed. Ideally, optimum start controls will start the system to provide just enough warm-up or cool-down time to bring the spaces served by the system to occupied setpoint temperatures at exactly the occupied hour, no sooner and no later. In practice, this ideal control is not possible but can be approached depending on the sophistication of the control algorithm. The Standard requires that the control algorithm must, as a minimum, be a function of the difference between space temperature and occupied setpoint and the amount of time prior to scheduled occupancy. More sophisticated algorithms include an adjustable or self-tuned mass/capacity factor that reflects the thermal mass of the building and the capacity of the heating and cooling systems. Optimum start controls are required for individual heating and cooling air distribution systems with a total design supply air capacity exceeding 10,000 cfm, served by one or more supply fans. Example 6-R—Time Controls, Equipment Room Cooling Unit Q An air conditioner serving an elevator equipment room in an office building and controlled by a thermostat that cycles the indoor supply fan and the compressor on calls for cooling. Does this unit need offhour controls so that it shuts off when the building is unoccupied at night? A No. The equipment must be maintained at a given temperature at all times and thus qualifies for Exception (b) to § 6.4.3.2. Furthermore, when the elevators are inactive at night, the air conditioner will automatically shutoff since there is no load in the space. Zone Isolation (§ 6.4.3.1.4) Large central systems often serve zones that are occupied by different tenants and may be occupied at different times. When only a part of the building served by the system is occupied, energy is wasted if unoccupied spaces are conditioned. To minimize this waste, the Standard requires that systems serving zones expected to User’s Manual for ANSI/ASHRAE/IESNA Standard 90.1-2007 Licensee=AECOM/5906698001, User=li, xiaoxiao Not for Resale, 07/02/2009 03:02:18 MDT --`,``,``,`,,,,,`````,`,```,```,-`-`,,`,,`,`,,`--- setback setpoint must be capable of being adjusted down to 55°F (13°C) or lower. ▪ Cooling system setup: Setup controls are required for cooling systems located where the cooling design temperature is greater than 100°F (38°C). The setup setpoint must be capable of being adjusted up to 90°F (32°C) or higher.