HVAC Mandatory Provisions
Setback controls prevent spaces from
becoming so cold, or so hot, during offhours that the HVAC system will not be
able to bring them back to a comfortable
range in a reasonable period of time. They
save energy because if they are not
present, systems in extreme climates are
often programmed to run 24 hours at least
part of the year to avoid under-cooled or
under-heated spaces in the morning or
possible damage to materials within the
building.
While setback controls are required to
have the setpoint capabilities listed above,
these setpoints may not be the optimum
for all applications. For buildings that are
massive, or where heating or cooling
capacity is marginal, it may be more
energy efficient to setback temperatures
only slightly from occupied setpoints.
(Radiant floor and low temperature ceiling
heating systems are exempt from set back
requirements for this reason; their
inherently slow pickup capability makes
only a slight setback possible.) The best
way to determine optimum setpoints is by
trial and error once the building and
system installations are complete.
Computer simulations are also possible
but not always accurate because of the
very complex ways that energy is
transferred into and out of and stored
within building mass.
Optimum Start Controls (§ 6.4.3.1.3)
The simplest time switch or scheduling
controls start systems each day based on
6-24
Copyright ASHRAE
Provided by IHS under license with ASHRAE
No reproduction or networking permitted without license from IHS
the time of day. To ensure that the space
is comfortable prior to occupancy, these
controls are typically scheduled to start
two or three hours prior to the expected
occupancy time to allow for warm-up or
cool-down. But this amount of warmup/cool-down time is not always required.
For instance, during mild weather, the
space may be very near comfort
conditions and require little or no warmup/cool-down period. To eliminate this
unnecessary system operating time,
optimum start controls were developed.
Ideally, optimum start controls will
start the system to provide just enough
warm-up or cool-down time to bring the
spaces served by the system to occupied
setpoint temperatures at exactly the
occupied hour, no sooner and no later. In
practice, this ideal control is not possible
but can be approached depending on the
sophistication of the control algorithm.
The Standard requires that the control
algorithm must, as a minimum, be a
function of the difference between space
temperature and occupied setpoint and the
amount of time prior to scheduled
occupancy. More sophisticated algorithms
include an adjustable or self-tuned
mass/capacity factor that reflects the
thermal mass of the building and the
capacity of the heating and cooling
systems. Optimum start controls are
required for individual heating and cooling
air distribution systems with a total design
supply air capacity exceeding 10,000 cfm,
served by one or more supply fans.
Example 6-R—Time Controls,
Equipment Room Cooling Unit
Q
An air conditioner serving an elevator
equipment room in an office building and
controlled by a thermostat that cycles the
indoor supply fan and the compressor on
calls for cooling. Does this unit need offhour controls so that it shuts off when the
building is unoccupied at night?
A
No. The equipment must be maintained at
a given temperature at all times and thus
qualifies for Exception (b) to § 6.4.3.2.
Furthermore, when the elevators are
inactive at night, the air conditioner will
automatically shutoff since there is no load
in the space.
Zone Isolation (§ 6.4.3.1.4)
Large central systems often serve zones
that are occupied by different tenants and
may be occupied at different times. When
only a part of the building served by the
system is occupied, energy is wasted if
unoccupied spaces are conditioned. To
minimize this waste, the Standard requires
that systems serving zones expected to
User’s Manual for ANSI/ASHRAE/IESNA Standard 90.1-2007
Licensee=AECOM/5906698001, User=li, xiaoxiao
Not for Resale, 07/02/2009 03:02:18 MDT
--`,``,``,`,,,,,`````,`,```,```,-`-`,,`,,`,`,,`---
setback setpoint must be capable of being
adjusted down to 55°F (13°C) or lower.
▪ Cooling system setup: Setup
controls are required for cooling systems
located where the cooling design
temperature is greater than 100°F (38°C).
The setup setpoint must be capable of
being adjusted up to 90°F (32°C) or
higher.