C.
5.
Section 26 0519: Low Voltage Wires (600 Volt AC).
6.
Section 26 2416: Panelboards and Signal Terminal Cabinets.
7.
Section 26 5200: Emergency Power Systems.
8.
Section 28 3100: Fire Detection and Alarm.
9.
Section 27 5313: Clock and Program System.
10.
Section 27 5127: Public Address Systems (Small Gyms, Multi-purpose
Rooms)(ES).
11.
Section 27 5128:
Public Address Systems (Auditoriums,
Performing Art, M-P Rooms)(MS and HS).
12.
Section 27 5129: Public Address Systems (Gymnasiums).
Acronyms:
DTMF
IC
LCD
OAR
PA
PBX
VFD
LED
SLC
1.02
Dual Tone Multiple Frequency
Intercom
Liquid Crystal Display
Owner Authorized Representative
Public Address
Private Branch Exchange
Vacuum Fluorescent Display
Light Emitting Diode
Small Learning Community
SYSTEM REQUIREMENTS
A.
Intercommunication System: System shall be a combined public address
and intercommunication system with UPS.
1.
Communication hardware shall be furnished with the capacity for
internal communication between operator and selected classrooms.
Normal and emergency alerts from classroom telephones to the
main office shall be annunciated by an alerting tone, appear on a
wall-mounted administrative display located where most office
staff can view at the same time, and identify the calling room’s
extension. These alerts shall function as described by the
manufacturer. Calls shall be displayed in the order in which they
are received and the additional calls stored in memory. The main
operator shall be able to answer calls in sequence or out of
sequence. Caution office staff during training about using any
que-clearing commands without verifying the nature of each call.
Dialed calls to classroom phones are initiated by ringing the
classroom telephone. These phones shall have their ringer volume
control locked in the maximum ring volume position. Dialed
intercom calls to the classroom speaker are preannounced by an
MODERNIZATION
OUR COMMUNITY SCHOOL
9/03/2014
PUBLIC ADDRESS AND INTERCOMMUNICATION SYSTEMS
27 5116-2