Appendix E
PLC Setup Coding Sheets for Programming Console
Address
61@@@@
A Input Time Constant Setting for General-purpose Inputs
Value (hex)
A
Input time constant
0000
0010
Default (8 ms)
0 ms (No filter)
0011
0012
0.5 ms
1 ms
0013
0014
2 ms
4 ms
0015
0016
8 ms
16 ms
0017
32 ms
Address
80@@@@
A
Value (hex)
A
IOM Hold Bit Status at
Startup
Forced Status Hold Bit
Status at Startup
C000
8000
Retained
Retained
Retained
Cleared
4000
0000
Cleared
Cleared
Retained
Cleared
Address
81@@@@
A
Display
A
Startup Mode
PRCN
PRG
Mode on Programming Console’s mode switch
PROGRAM mode
MON
RUN
MONITOR mode
RUN mode
Address
128@@@@
A
Value (hex)
A
494
C000
Low Battery Voltage
Detection
Do not detect.
Interrupt Task Error
Detection
Do not detect.
8000
4000
Do not detect.
Detect.
Detect.
Do not detect.
0000
Detect.
Detect.