Download Controller - AHI Carrier

Transcript
Writing the hydronic configuration in all NTC controllers.
When writing is completed, the "Next" button is displayed.
6.2.11 - Step 11 - Selection of the chillers (chapter 9.7.3)
6.2.13 - Step 13 - Data profile of the air handling unit(s)
If no air handling unit is used, it is sufficient to specify that
the NSM does not control the AHU and go to the next step.
If this is a Carrier unit equipped with electronic Pro-Dialog+
control, the water production unit is a CCN unit. Specify
the unit CCN address on the primary bus (default is 1).
NOTE: If there is a master/slave configuration between
two Pro-Dialog units, only the master unit is controlled
by the NSM. It is therefore preferable to use address 2, for
example, for the slave unit.
If the air handling unit is not a CCN unit its control by the
NSM must be authorised and it must be indicated that it is
not CCN. Its start/stop command will be attributed to
digital output 3 by default.
If the AHU(s) is a (are) communicating Carrier units, its
(their) control by the NSM must be authorised and it must
be indicated that it is (they are) CCN.
If the chiller/heat pump is not a CCN unit, its start/stop
control will be assigned to digital output 1 by default. If
the hot water is produced by a boiler, it is automatically
given a digital output (output 2 by default).
6.2.12 - Step 12 - Data profile of the CCN chiller
This step is available if the chiller/heat pump is a CCN unit.
The NSM reads all CCN tables of the chiller/heat pump.
This step can take several minutes. The following screen is
displayed once the process has been completed.
Proceed as follows:
• If only one AHU is present, tick the box "Search for
addressed units" so that the NSM can retrieve its
identifier,
• If several AHUs are present and at the same CCN
address (24 by default), unclick this box and go to the
next step,
• If several AHUs are present and at addresses between
24 and 31, tick this box so that the NSM can retrieve
their identifiers.
NOTES:
• The NSM autorises a single non-CCN AHU or up to
eight CCN AHUs (exclusive).
• For the AHUs only the CCN addresses from 24 to 31
are autorised.
17