Download Controller - AHI Carrier
Transcript
Writing the hydronic configuration in all NTC controllers. When writing is completed, the "Next" button is displayed. 6.2.11 - Step 11 - Selection of the chillers (chapter 9.7.3) 6.2.13 - Step 13 - Data profile of the air handling unit(s) If no air handling unit is used, it is sufficient to specify that the NSM does not control the AHU and go to the next step. If this is a Carrier unit equipped with electronic Pro-Dialog+ control, the water production unit is a CCN unit. Specify the unit CCN address on the primary bus (default is 1). NOTE: If there is a master/slave configuration between two Pro-Dialog units, only the master unit is controlled by the NSM. It is therefore preferable to use address 2, for example, for the slave unit. If the air handling unit is not a CCN unit its control by the NSM must be authorised and it must be indicated that it is not CCN. Its start/stop command will be attributed to digital output 3 by default. If the AHU(s) is a (are) communicating Carrier units, its (their) control by the NSM must be authorised and it must be indicated that it is (they are) CCN. If the chiller/heat pump is not a CCN unit, its start/stop control will be assigned to digital output 1 by default. If the hot water is produced by a boiler, it is automatically given a digital output (output 2 by default). 6.2.12 - Step 12 - Data profile of the CCN chiller This step is available if the chiller/heat pump is a CCN unit. The NSM reads all CCN tables of the chiller/heat pump. This step can take several minutes. The following screen is displayed once the process has been completed. Proceed as follows: • If only one AHU is present, tick the box "Search for addressed units" so that the NSM can retrieve its identifier, • If several AHUs are present and at the same CCN address (24 by default), unclick this box and go to the next step, • If several AHUs are present and at addresses between 24 and 31, tick this box so that the NSM can retrieve their identifiers. NOTES: • The NSM autorises a single non-CCN AHU or up to eight CCN AHUs (exclusive). • For the AHUs only the CCN addresses from 24 to 31 are autorised. 17