Download DeviceNet Master Module: JW-50DN2

Transcript
JW-D164NH to D165MH
Appendix 1: JW-D164NH/D162SH/D165SH/D162MH/D165MH
This section gives the names and functions of each part of the JW-D164NH/D162SH/D165SH/D162MH/
D165MH (hereafter referred to as "this slave").
Appendix 1-1: Names and functions of each part
1 Indicator lamp
Shows communication, input, and output status
for the DeviceNet. => App-4 and App-5.
2 Terminal block cover
Protects the terminal block.
3 Terminal block (26-pin, detachable type, M3.5 x
7 screws)
Connect the DeviceNet communication, power
supply, input and output cables.
4 Module installation holes (ø4: 2 positions)
Holes for installing a module using M3 screws.
5 DIN rail lever
Used to install and remove the module on a DIN
rail.
6 Switch (with cover)
Assigns a node address for the DeviceNet.
=> See below.
④
①
⑥
②
③
④
⑤
(1) Switch
・JW-D162SH/D165SH/D162MH/D165MH
32
16
8
4
2
1
D
R
D 1
R
O 0
F
O F
FF
32
16
8
4
2
1
D
R
D 1
R
O 0
F
H F
O
LD
・JW-D164NH
(Default:
All OFF except the HOLD)
(Default: All OFF) ON
ON
NODE ADRS.
Switch
HOLD
OFF
DR0
DR1
NODE ADRS.
Setting details
Set the output status to use when this slave has a communication error.
OFF Clear
ON Hold
Make sure to set to OFF. (JW-D164NH has two switches)
Specify the data communication speed.
DR1
DR0
Communication speed
OFF
OFF
125kbps
OFF
ON
250kbps
ON
OFF
500kbps
ON
ON
Unavailable
[Setting example]
Using the JW-D162SH, set the
output status to use when an error
occurs to "HOLD," set the
communication speed to 125 kbps,
and assign node address 10.
32
16
8
4
2
1
D
R
D 1
R
O 0
F
H F
O
LD
Specify the node address (0 to 63 in decimal).
NODE ADRS.
- Specify a node address that does not duplicate another node address in
(32, 16, 8, 4, 2, 1)
the same network.
ON
NODE ADRS.
App-2
ON
(All OFF except the ON)