Download MELSEC-L CPU Module User`s Manual (Function Explanation
Transcript
CHAPTER 3 CPU MODULE FUNCTIONS 3.4 Latch Function This function holds data in each device of the CPU module when: • the CPU module is powered off and then on, • the CPU module is reset, or • a power failure occurred exceeding the allowable momentary power failure time. 3 Data in each device of the CPU module are cleared and set back to its default (bit device: off, word device: 0) when this function is not used. By using this function, the operation can be continued with the previous data even after powering off the CPU module while the data are managed by a sequential control. Program operation does not change regardless of the latch (1) Devices that can be latched Set the device to latch among the following. (By default, only the latch relay is latched.) • Latch relay (L) • Link relay (B) • Annunciator (F) • Edge relay (V) • Timer (T) • Retentive timer (ST) • Counter (C) • Data register (D) • Link register (W) The following devices also can be set when a file register is set to be used in the PLC file. • File register (ZR) • Extended data register (D) When the battery life-prolonging function is set, the latch function is disabled. ( • Extended link register (W) Page 169, Section 3.30) 3.4 Latch Function (2) Latch range setting Set the following. Project Window [Parameter] [PLC Parameter] [Device] • Latch clear is enabled (Latch (1) Start/End): The latch range that can be cleared by remote latch clear operation • Latch clear is disabled (Latch (2) Start/End): The latch range that cannot be cleared by remote latch clear operation Set latch ranges by the start and end device numbers. 85