Download Chapter 7 Communications
Transcript
Chapter 7 Communications 7-4-3 Loop-back Test (Function Code: 08 Hex) H Settings and Response • The DSR message from the Master is returned as a response. The Inverter does not retrieve or process this data. • The DSR message or normal response for loop-back test use is divided into 8-byte blocks as shown below. Any data can be set as test data 1 or 2 provided that the number of data items remains changed. • This command is used for checking the status of communications or for dummy communications without detecting any communications time-over. D DSR Message Byte No. 1 2 3 4 5 6 7 8 Data Slave address Function code (08 Hex) Test data 1 Test data 2 CRC-16 check D Response Normal Byte No. 1 2 3 4 5 6 7 8 Data Slave address Function code (08 Hex) Test data 1 Test data 2 CRC-16 check Error Byte No. 1 2 3 4 5 Data Slave address Function code (88 Hex) Error code CRC-16 check Note When an error occurs, the MSB of the function code will be set to 1. 7-18