Download P2000 Security Management System Software Release Notes

Transcript
P2000 Version 3.12 SP3
Software Release Notes
24-10685-149 Rev. D
The following issues have been solved in P2000 Software Version 3.12 SP1.
Problems Fixed in Version 3.12 SP1
Alarms
The Alarm Response text application crashes when user clicks
the Text column in the Alarm Response Text window.
(Defect #5685)
Cardholder Definition
A UDF choice value assigned to one or more cardholders is
deleted from all cardholders when you edit and then cancel a
choice value for the associated UDF. (Defect #5763)
CK7xx Controllers
CK7xx controllers cannot connect to a P2000 Server when the
FDA Part 11 feature is enabled. (Defect #3324)
Database Maintenance The digital signatures of some database tables are incorrectly
and Validating Digital reported as failing during system validation. (Defect #3249)
Signatures
DVR/VMS: Bosch
After installing a Bosch DVR, the following message appears in
the RTL: “Bosch Interface Service not configured to start.”
(Defect #5684)
DVR/VMS: Milestone
When a Milestone MIP switch is configured, no record of the
switch being configured is stored in the AVPreset_save table.
(Defect #3276)
DVR/VMS: Pelco
Endura
When viewing two cameras in multiple panes view, the playback
function does not work for the second camera. (Defect #5857)
Mercury Intrusion
Alarm generated while system is disarmed changes to “Armed/
Alarmed” in the P2000 system. (Defect #5683)
P2000 Software
Upgrade
Upgrade to P2000 Version 3.12 generates an error message.
(Defect #5923)
Panel Configuration
You cannot edit the S321-IP terminal name. (Defect #5865)
Panel Configuration:
Kone IP Controller
When a Kone IP controller is created and then deleted in P2000,
the delete record is not downloaded to the panel. (Defect #5648)
Reports
When you run a P2000 report in Arabic, Crystal Reports does
not display P2000 data. (Defect #5646)
System Status
System Status shows that Mercury panel is up even when the
Mercury Service is stopped. (Defect #5764)
S321-IP
S321 IP panel goes up and down when configured in P2000
SMS with the FDA option enabled. (Defect #5662)
XML-RMS Real Time
Data Message
The XML-RMS Real Time Data Message for History Type 35
(Invalid Reader) omits the CardholderID. (Defect #5765)