SECTION 12: Appendix
80
EXAMPLE
12.5 SIZING TANKS
Assume we want 16 GPM at 60 PSI from a pump drawdown level (pumping level) 100 feet below the service
inlet.
Tanks should be sized to allow the pump to be off for at
least one minute between starts.
Refer to the dealer catalog for tank selection. Otherwise,
the following procedure can be used.
We have a 35 foot horizontal run of 1 1/4" Plastic pipe
with two gate valves and (4) 90° elbows.
Drawdown based on Boyle’s Law
To find the Friction losses we must refer to friction loss
charts for pipe and fittings.
PROCEDURE:
We find:
• 135 feet of pipe for the total pipe run (100 + 35).
1. Identify drawdown multiplier relating to specific
application.
• 10 equivalent feet of pipe for the gate valves (2 x5)
2. Insert multiplier (X) into the following formula:
Pump GPM x Min Run Time
= Minimum Tank
Capacity Required
Multiplier (X)
• 28 equivalent feet of pipe for the elbows (7x 4)
Add these for the total equivalent length of pipe = 173
• In the friction loss charts, find the loss of head for 173
feet of 1 1/4” pipe at 16 gpm. (3.96 per 100’) = 3.96 x
1.73 = 6.8 (round to 7.0)
Add:
7
Friction loss
100
Pumping level
139
60 PSI service pressure required (60 x
2.31=138.6. Round to 139)
Total Dynamic Head.
= 246.0
Locate a pump with a best efficiency point near the desired
flow rate (16 GPM) that meets the total head requirements
(246 TDH).
Selecting a pump in this manner gives you the most
efficient pump for your application.
CAPACITY LITRES PER MINUTE
0
25
50
75
100
600
175
500
Example: An example of a 20 GPM pump with a minimum
run time of 1 minute, installed on a 50 - 70 PSIG
system pressure range:
20 GPM x 1 minute
= 83.3 minimum U.S.
gallon tank capacity
.24 (factor) from Chart B
NOTICE: Drawdown will be affected by operating
temperature of the system, accuracy of the pressure switch
and gauge, the actual precharge pressure and the rate of
fill.
From this sample curve we would choose the 1 1/2 HP
pump.
TABLE 12-2: Drawdown Volume Multiplier
(Approximate)
Pump Off
Pressure
10
PSI
20
0.26
30
0.41
40
50
60
70
80
90
100
Pump Start Pressure – PSI
20
0.22
0.37
0.46
30
0.18
0.31
0.40
0.47
40
0.15
0.27
0.35
0.42
0.48
50
60
70
80
0.13
0.24
0.32
0.38
0.44
0.12
0.21
0.29
0.35
0.11
0.19
0.26
0.10
0.17
150
125
2H
400
P
1-1/
2 HP
100
300
1 HP
75
200
50
100
25
0
0
5
10
15
20
25
CAPACITY GALLONS PER MINUTE
PN793
30
TOTAL HEAD IN METERS
TOTAL HEAD IN FEET
PN793
Tank sizing for Variable Frequency Drives
Variable Frequency Drives (VFD) may require slightly
different methods for figuring tank size. Refer to Section 8
for VFD information.