Download manual - Sta-Rite
Transcript
11/20/09 9:21 AM Page 80 SECTION 12: Appendix 80 EXAMPLE 12.5 SIZING TANKS Assume we want 16 GPM at 60 PSI from a pump drawdown level (pumping level) 100 feet below the service inlet. Tanks should be sized to allow the pump to be off for at least one minute between starts. Refer to the dealer catalog for tank selection. Otherwise, the following procedure can be used. We have a 35 foot horizontal run of 1 1/4" Plastic pipe with two gate valves and (4) 90° elbows. Drawdown based on Boyle’s Law To find the Friction losses we must refer to friction loss charts for pipe and fittings. PROCEDURE: We find: • 135 feet of pipe for the total pipe run (100 + 35). 1. Identify drawdown multiplier relating to specific application. • 10 equivalent feet of pipe for the gate valves (2 x5) 2. Insert multiplier (X) into the following formula: Pump GPM x Min Run Time = Minimum Tank Capacity Required Multiplier (X) • 28 equivalent feet of pipe for the elbows (7x 4) Add these for the total equivalent length of pipe = 173 • In the friction loss charts, find the loss of head for 173 feet of 1 1/4” pipe at 16 gpm. (3.96 per 100’) = 3.96 x 1.73 = 6.8 (round to 7.0) Add: 7 Friction loss 100 Pumping level 139 60 PSI service pressure required (60 x 2.31=138.6. Round to 139) Total Dynamic Head. = 246.0 Locate a pump with a best efficiency point near the desired flow rate (16 GPM) that meets the total head requirements (246 TDH). Selecting a pump in this manner gives you the most efficient pump for your application. CAPACITY LITRES PER MINUTE 0 25 50 75 100 600 175 500 Example: An example of a 20 GPM pump with a minimum run time of 1 minute, installed on a 50 - 70 PSIG system pressure range: 20 GPM x 1 minute = 83.3 minimum U.S. gallon tank capacity .24 (factor) from Chart B NOTICE: Drawdown will be affected by operating temperature of the system, accuracy of the pressure switch and gauge, the actual precharge pressure and the rate of fill. From this sample curve we would choose the 1 1/2 HP pump. TABLE 12-2: Drawdown Volume Multiplier (Approximate) Pump Off Pressure 10 PSI 20 0.26 30 0.41 40 50 60 70 80 90 100 Pump Start Pressure – PSI 20 0.22 0.37 0.46 30 0.18 0.31 0.40 0.47 40 0.15 0.27 0.35 0.42 0.48 50 60 70 80 0.13 0.24 0.32 0.38 0.44 0.12 0.21 0.29 0.35 0.11 0.19 0.26 0.10 0.17 150 125 2H 400 P 1-1/ 2 HP 100 300 1 HP 75 200 50 100 25 0 0 5 10 15 20 25 CAPACITY GALLONS PER MINUTE PN793 30 TOTAL HEAD IN METERS TOTAL HEAD IN FEET PN793 Tank sizing for Variable Frequency Drives Variable Frequency Drives (VFD) may require slightly different methods for figuring tank size. Refer to Section 8 for VFD information.