Chapter 11: F0-4AD2DA-1 4-Ch. In/2-Ch. Out Analog Current Combination
The following tables provide the specifications for the F0–4AD2DA–1 Analog Combination
Module. Review these specifications to make sure the module meets your application
requirements.
Input Specifications
Number of Channels
Input Range
Resolution
Step Response
Crosstalk
Active Low-pass Filtering
Input Impedance
Absolute Maximum Ratings
Converter type
Linearity Error (End to End)
Input Stability
Full Scale Calibration Error
(Offset error not included)
Offset Calibration Error
4, single ended (one common)
0 to 20 mA or 4 to 20 mA (jumper selectable)
12 bit (1 in 4096) for 0-20mA, scaled for 4-20mA
25.0 ms (typ) to 95% of full step change
-80 dB, 1/2 count maximum *
-3 dB at 40Hz (-12 dB per octave)
125 Ohm _0.1%, 1/8 W current input
-30 mA to +30 mA current input
Successive approximation
±2 counts
± 1 count *
± 10 counts maximum @ 20mA current input*
± 5 counts maximum @ 0mA current input *
±.4% @ 25°C (77°F)
Maximum Inaccuracy
±.85% 0 to 60°C (32 to 140°F)
±100 ppm typical full scale calibration
Accuracy vs. Temperature
(including maximum offset change)
Recommended Fuse (external)
0.032 A Series 217 fast-acting, current inputs
*One count in the specification table is equal to one least significant bit of the analog data value (1 in 4096).
Output Specifications
Number of Channels
Output Range
Output Type
Resolution
Maximum Loop Voltage
Load (ohms)/Loop Power Supply
Linearity Error (end to end)
Conversion Settling Time
Full Scale Calibration Error
Note: Error depends on the load from
source terminal to ground.
2, single ended (one common)
4 to 20 mA or 0 to 20 mA (jumper selectable)
Current sourcing
12 bit (1 in 4096) for 0 to 20 mA, scaled for 4 to 20 mA
30 VDC
0-300/18-30V
± 2 counts (± 0.050% of full scale) maximum *
400µS max. full scale change
± 26 counts max. @ 300⏲ load
± 18 counts max. @ 250⏲ load
± 12 counts max. @ 125⏲ load
± 10 counts max. @ 300⏲ load
± 8 counts max @ 250⏲ load
Offset Calibration Error
± 6 counts max. @ 125⏲ load
300⏲ load 0.4% @ 60°C
Max. Full Scale Inaccuracy
250⏲ load 0 3%@60°C
(% of full scale) all errors included
125⏲ load 0.2% @ 60°C
* One count in the specification tables is equal to one least significant bit of the analog data value (1 in 4096).