Download Chapter 11 - AutomationDirect
Transcript
Chapter 11: F0-4AD2DA-1 4-Ch. In/2-Ch. Out Analog Current Combination The following tables provide the specifications for the F0–4AD2DA–1 Analog Combination Module. Review these specifications to make sure the module meets your application requirements. Input Specifications Number of Channels Input Range Resolution Step Response Crosstalk Active Low-pass Filtering Input Impedance Absolute Maximum Ratings Converter type Linearity Error (End to End) Input Stability Full Scale Calibration Error (Offset error not included) Offset Calibration Error 4, single ended (one common) 0 to 20 mA or 4 to 20 mA (jumper selectable) 12 bit (1 in 4096) for 0-20mA, scaled for 4-20mA 25.0 ms (typ) to 95% of full step change -80 dB, 1/2 count maximum * -3 dB at 40Hz (-12 dB per octave) 125 Ohm _0.1%, 1/8 W current input -30 mA to +30 mA current input Successive approximation ±2 counts ± 1 count * ± 10 counts maximum @ 20mA current input* ± 5 counts maximum @ 0mA current input * ±.4% @ 25°C (77°F) Maximum Inaccuracy ±.85% 0 to 60°C (32 to 140°F) ±100 ppm typical full scale calibration Accuracy vs. Temperature (including maximum offset change) Recommended Fuse (external) 0.032 A Series 217 fast-acting, current inputs *One count in the specification table is equal to one least significant bit of the analog data value (1 in 4096). Output Specifications Number of Channels Output Range Output Type Resolution Maximum Loop Voltage Load (ohms)/Loop Power Supply Linearity Error (end to end) Conversion Settling Time Full Scale Calibration Error Note: Error depends on the load from source terminal to ground. 2, single ended (one common) 4 to 20 mA or 0 to 20 mA (jumper selectable) Current sourcing 12 bit (1 in 4096) for 0 to 20 mA, scaled for 4 to 20 mA 30 VDC 0-300/18-30V ± 2 counts (± 0.050% of full scale) maximum * 400µS max. full scale change ± 26 counts max. @ 300⏲ load ± 18 counts max. @ 250⏲ load ± 12 counts max. @ 125⏲ load ± 10 counts max. @ 300⏲ load ± 8 counts max @ 250⏲ load Offset Calibration Error ± 6 counts max. @ 125⏲ load 300⏲ load 0.4% @ 60°C Max. Full Scale Inaccuracy 250⏲ load 0 3%@60°C (% of full scale) all errors included 125⏲ load 0.2% @ 60°C * One count in the specification tables is equal to one least significant bit of the analog data value (1 in 4096). DL05/06 Option Modules User Manual; 7th Ed. Rev. A, 08/11 1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 11–3