Download Programming manual
Transcript
Configuration Mode - Complete menu (FULL) I-OdrCCtLFUNFLtCOM- High speed configuration The logic inputs enable selection of the desired high speed. Desired High speed Setting Parameter State HSP SH2 nO SH4 nO SH2 assigned SH4 nO SH2 nO SH4 assigned SH2 assigned SH4 assigned HSP2 HSP3 HSP4 Code Name/Description Adjustment range Factory setting LSP to tFr 50 or 60 Hz according to BFr, max TFr Function menu (continued) FUnSPL- Speed limit menu M High speed HSP T Motor frequency at maximum reference, can be set between Low speed LSP and Maximum frequency tFr page 55. If tFr is decreased below the value defined for HSP, then HSP automatically decreases to the new value of tFr. This parameter is already included in "my menu" section, page 44. SH2 nO L1H L2H L3H L4H SH4 nO L1H L2H L3H L4H HSP2 T T 76 M 4 HSP assignment v No v L1h: LI1 active high v L2h: LI2 active high v L3h: LI3 active high v L4h: LI4 active high nO M High speed 2 LSP to tFr as HSP M High speed 3 LSP to tFr as HSP LSP to tFr as HSP Visible only if 4 HSP assignment SH4 is not set to nO. HSP4 T nO Visible only if 2 HSP assignment SH2 is not set to nO. HSP3 T M 2 HSP assignment v No v L1h: LI1 active high v L2h: LI2 active high v L3h: LI3 active high v L4h: LI4 active high M High speed 4 Visible only if 2 HSP assignment SH2 and 4 HSP assignment SH4 are not set to nO. Parameter that can be modified during operation or when stopped. BBV28581 04/2009