Download EXPERT VT110
Transcript
EXPERT VT110 6.2.1.2. Variable-Speed Fans 6.2. Fan Stages 6.2.1. Principle of Operation 6.2.1.1. Operation of Fan Stages The controller has 8 fan stages which operate in a sequence to increase the level of ventilation as the room temperature increases. Each stage can activate two variable outputs, on/off outputs, and a combination of timer relays for cooling purposes. A fan stage is activated when the room temperature reaches its start temperature and is disabled when the room temperature decreases to its stop temperature. Ventilation Level Transition between fan stages 1 and 2 If the next stage is an ON/OFF fan stage, the variable output is deactivated when the new stage starts. If the next stage is another variable fan stage, the speed of the first variable stage is reduced to its minimum speed when the second variable stage starts. This ensures a smooth transition between both stages. Variable outputs are activated when their associated fan stage starts (see section 4.9). They start running at their absolute minimum speed (see section 4.5) and their speed gradually increases as the room temperature increases. Variable outputs reach their full speed when the start temperature of the following fan stage is reached. 100% The bandwidth is the temperature interval over which variable outputs go from their minimum to their maximum speed. This is true even if full speed is never reached as in the example below: when stage 2 starts, the controller decreases the speed of variable outputs to the initial speed associated with stage 2. It then uses the bandwidth to increase the fan speed as the room temperature rises. Min Speed If an outdoor temperature probe is used, it is possible the controller can automatically adjust bandwidths 1-2 as a function of the outdoor temperature (see below). Fan Speed Operating Diagram of Variable-Speed Fans Operating Diagram of Fan Stages Stg y Stage x+1 On T° Stage x On T° Set Point Stage y On T° Stage y Off T° Stage x On T° Stage x Off T° Set Point Room T° Stage x Off T° Room T° Stg x Transition between Stages 1 & 2 Speed of variable fans 1 V1 Bandwidth 16 EXPERT VT110 rev.15 Absolute Min speed 0.3°F V1 Bandwidth Room T° Stage 3 On T° Stage 2 On T° Off Stage 2 Off T° Timer-based relays in fan stages Fan stages can activate relays that operate following a timer (On and Off Times). This is useful to activate misting units in timer mode while a specific fan stage is active. Refer to section 4.7.4 to enable timer-based relays. Stage 1 On T° Start temperatures of fan stages are defined with respect to the set point and with respect to each other. This means that when one of these values is adjusted, all the consecutive values are adjusted by the same amount. For example, if the set point is increased by 1°F, the start temperature of all fan stages will be increased by the same amount. 100%