BEFORE USING ANY ANALYZER CHECK THAT: - Calibration date has not expired Particle filter is not dirty inside Water trap and flue probe hose are empty of water Water trap is fitted correctly to the analyzer including the drain plug Flue probe hose is connected properly to the flue gas inlet Flue probe temperature plug is connected into T1 connection Please read the Safety Warnings in the User Manual USING THE ANALYZER With the flue probe in fresh air at the same temperature as the boiler inlet air press . The analyzer will auto-calibrate for 20 to 30 seconds and then a set of readings will be displayed. In fresh air the O2 reading should be 20.9% + 0.1% and the CO reading should be zero. Check the battery status by selecting “Bat” on the rotary switch and select the correct fuel via the “menu” – See Using the Menu. Insert the tip of the probe into the center of the flue. After approximately 60 seconds the readings should stabilize. A printout can be produced if required by pressing . SETTING UP THE DISPLAY Any four parameters can be displayed simultaneously. Press to move the line select LED to the line you wish to change, then use the rotary switch to select the new parameter you require. To change other lines just repeat the procedure.