Download EXPERT PN110
Transcript
EXPERT PN110 5.6 Natural Ventilation 5.6.1 Principle of Operation De-icing/Purge The controller controls up to 2 independent curtains for natural ventilation. These curtains operate according to the average temperature of their respective zone. When temperature increases and exceeds their Start Opening Temperature, the curtains open according to an Opening Cycle; likewise, they close according to a Closing Cycle when temperature decreases below their Stop Closing Temperature. Each curtain operates according to the average tempreature reading of chosen temperature probes. Refer to section 5.16.9 to assign these probes. The de-icing/purge option consists in opening the curtain on a short period of time to prevent the formation of ice on the membrane. This function can be enabled all the time or on cold days only. Refer to section 5.17.4.1 to select when this function must be used. De-icing / purge cycle When a de-icing cycle starts, the curtain opens during the "Purge Move Time" and remains opened during the "Purge Delay". The curtain finally returns to its initial position when the "Purge Delay" is over. The next de-icing/purge cycle takes place after the "Purge Cycle" time. Natural Ventialtion Curtain Status The curtain closes in timer mode The curtain opens for the first time during its initial open time. The curtain opens in timer mode T° Set Point 28 Start Close at EXPERT PN110 rev.12 Initial Open at Start Open at